Technical specifications
6.3 Derating data
Power Module PM330
82
Hardware Installation Manual, 10/2016, A5E32844552B AD
Article No.
6SL3310-
1PG35-8AA0
1PG36-5AA0
1PG37-2AA0
Recommended cable cross-section for 500 V
- line cable
- motor cable
3)
2 x 240 mm
2
2 x 185 mm²
3 x 185 mm
2
2 x 240 mm²
3 x 185 mm
2
2 x 240 mm²
Recommended cable cross-section for 690 V
- line cable
- motor cable
3)
2 x 240 mm
2
2 x 185 mm²
3 x 150 mm
2
2 x 240 mm²
3 x 185 mm
2
2 x 240 mm²
Recommended cable cross-section for 500 V
- DC link infeed (2/3 converter power)
2 x 185 mm
2
2 x 185 mm
2
2 x 240 mm
2
Recommended cable cross-section for 690 V
- DC link infeed (2/3 converter power)
2 x 150 mm
2
2 x 185 mm
2
2 x 185 mm
2
Tightening torque for line, motor, DC link, and
ground cable
50 Nm / 443 lbf in
50 Nm / 443 lbf in
50 Nm / 443 lbf in
Dimensions: Width x height x depth [mm]
801 x 1621 x 393
801 x 1621 x 393
801 x 1621 x 393
Weight
234 kg
234 kg
244 kg
1)
The line supply must be capable of supplying the minimum short-circuit current so that the fuses rupture and conse-
quential damage is avoided.
Note: If the minimum short-circuit current is not reached, the rupture time for the fuses increases, which may result in
consequential damage.
2)
When semiconductor fuses are used, they must be mounted in the same higher construction as the converter.
3)
The motor cables must be evenly distributed at both connection chambers.
6.3
Derating data
6.3.1
Derating factor of the output current as a function of the operating temperature
Figure 6-3
Derating factor of the output current as a function of the operating temperature
Содержание SINAMICS G120P PM330