Technical specifications
6.2 Specific technical data
Power Module PM330
Hardware Installation Manual, 10/2016, A5E32844552B AD
73
Table 6- 3
PM330, frame size HX, 3-phase 380 … 480 VAC
Article no.
6SL3310-
1PE35-8AA0
1PE36-6AA0
1PE37-4AA0
Rated input current
- at 380/400 V, 40° C
- at 480 V, 40° C
- at 380/400 V, 50° C
- at 480 V, 50° C
597 A
497 A
507 A
422 A
668 A
536 A
568 A
456 A
750 A
614 A
637 A
522 A
Rated input current DCP/DCN
(for 2/3 of the converter power)
- at 510 V
DC
, 40 °C
- at 650 V
DC
, 40 °C
- at 510 V
DC
, 50 °C
- at 650 V
DC
, 50 °C
498 A
415 A
423 A
352 A
558 A
448 A
474 A
381 A
626 A
513 A
532 A
436 A
Rated output current I
N
- at 380/400 V, 40° C
- at 480 V, 40° C
- at 380/400 V, 50° C
- at 480 V, 50° C
585 A
487 A
497 A
414 A
655 A
526 A
557 A
447 A
735 A
602 A
625 A
512 A
LO base load power
LO base load input current at 400 V
LO base load output current at 400 V
315 kW
581 A
570 A
355 kW
653 A
640 A
400 kW
734 A
720 A
HO base load power
HO base load input current at 400 V
HO base load output current at 400 V
250 kW
477 A
468 A
250 kW
501 A
491 A
315 kW
562 A
551 A
Fuse according to IEC
Manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1437-2
(710 A/690 V)
Siemens AG
≤ 100 kA
> 10.0 kA
3NE1438-2
(800 A/690 V)
Siemens AG
≤ 100 kA
> 11.0 kA
3NE1448-2
(850 A/690 V)
Siemens AG
≤ 100 kA
> 13.0 kA
Fuse in compliance with UL
2)
Manufacturer:
Maximum permissible line short-circuit current I
kmax
Minimum line short-circuit current required I
kmin
1)
3NE1437-2
(710 A/690 V)
Siemens AG
≤ 100 kA
> 10.0 kA
3NE1438-2
(800 A/690 V)
Siemens AG
≤ 100 kA
> 11.0 kA
3NE1448-2
(850 A/690 V)
Siemens AG
≤ 100 kA
> 13.0 kA
max. power loss, at I
N
, 40 °C, 400 V
6.791 kW
7.687 kW
8.385 kW
Required cooling air flow
360 l/s
360 l/s
360 l/s
Maximum connectable cross-section of the line,
motor and DC-link cable
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
Recommended cable cross-section for 380 V/400 V
- line cable
- motor cable
2 x 240 mm
2
2 x 185 mm²
3 x 150 mm
2
2 x 240 mm²
3 x 185 mm
2
2 x 240 mm²
Recommended cable cross-section for 480 V
- line cable
- motor cable
2 x 185 mm
2
2 x 150 mm²
2 x 240 mm
2
2 x 185 mm²
2 x 240 mm
2
2 x 240 mm²
Recommended cable cross-section for 380 V/400 V
- DC link infeed (2/3 converter power)
- Braking Module
3)
2 x 185 mm
2
35 mm²
2 x 240 mm
2
35 mm²
3 x 150 mm
2
35 mm²
Recommended cable cross-section for 480 V
- DC link infeed (2/3 converter power)
- Braking Module
3)
2 x 150 mm
2
35 mm²
2 x 185 mm
2
35 mm²
2 x 240 mm
2
35 mm²
Содержание SINAMICS G120P PM330
Страница 1: ......
Страница 2: ......
Страница 18: ...Introduction Power Module PM330 18 Hardware Installation Manual 10 2016 A5E32844552B AD ...
Страница 94: ...Appendix A 3 Abbreviations Power Module PM330 94 Hardware Installation Manual 10 2016 A5E32844552B AD ...
Страница 97: ......
Страница 98: ......