Connecting up, switching on
4.6 EMC compliant connection
Power Module PM330
Hardware Installation Manual, 10/2016, A5E32844552B AD
55
Additional measures
Finely stranded, braided copper cables have to be routed in parallel with the cable shields in
the following cases:
●
Old installations with existing unscreened cables
●
Cables with poor high-frequency properties of the shield
●
Installations with bad grounding systems
Connections shown in the following diagram offer a durable, high-frequency equipotential
bonding between the motor enclosure, the motor terminal box, the driven load and the EMC
rail/busbar.
Figure 4-15 Additional high-frequency bonding of the drive system