Technical specifications
6.2 Specific technical data
Power Module PM330
74
Hardware Installation Manual, 10/2016, A5E32844552B AD
Article no.
6SL3310-
1PE35-8AA0
1PE36-6AA0
1PE37-4AA0
Tightening torque for line, motor, DC link, and
ground cable
50 Nm / 443 lbf in
50 Nm / 443 lbf in
50 Nm / 443 lbf in
Dimensions: Width x height x depth (mm)
548 x 1695 x 393
548 x 1695 x 393
548 x 1695 x 393
Weight
155 kg
155 kg
157 kg
Minimum control cabinet size for installation of the
Power Module (width x height x depth)
800 mm x 2000 mm x 600 mm
1)
The line supply must be capable of supplying the minimum short-circuit current so that the fuses trigger and consequen-
tial damage is avoided.
Note: If the minimum short-circuit current is not reached then the tripping time for the fuses increases, and this may
result in consequential damage.
2)
When semiconductor fuses are used, they must be mounted in the same higher construction as the converter.
3)
When connecting a Braking Module with rated power 50 kW, P
20
power 200 kW.