03.99
Communication via CC-Link
Siemens AG
6SE7087-6NX84-0GB0
SIMOVERT MASTERDRIVES
Operating Instructions
4-1
4
Communication via CC-Link
4.1
CC-Link profile of SIMOVERT MASTERDRIVES
At CC-Link there are standard profiles for inverters, displays,
analog/digital converters, etc. CBL confirms to the profile for inverters.
The standard profile for inverters has 32 I/O control and status bits and
4 registers with 16 bit data.
I/O bit structure
Master -> Remote
Remote -> Master
Device No. Signal name
Device No. Signal name
RYn0
Forward command (STF)
RXn0
Forward operation
RYn1
Reverse command (STR)
RXn1
Reverse operation
RYn2
High speed (RH)
RXn2
Running (RUN)
RYn3
Medium speed (RM)
RXn3
Frequency reached (SU)
RYn4
Low speed (RL)
RXn4
Overload (OL)
RYn5
JOG 1 mode (JOG1)
RXn5
Momentary power failure(IPF)
RYn6
Second Acceleration/decel. time Selection (RT)
RXn6
Frequency detection (FU)
RYn7
JOG 2 mode (JOG2)
RXn7
Abnormal (ABC)
RYn8
Option flag 27 (F27)
RXn8
Info flag 0 (I0)
RYn9
Output stop (MRS)
RXn9
Info flag 7 (I7)
RYnA
Option flag 28 (F28)
RXnA
Info flag 15 (I15)
RYnB
Option flag 29 (F29)
RXnB
Unused
RYnC
Monitor command
RXnC
Monitoring
RYnD
Frequency set command (RAM)
RXnD
Frequency setting complete (RAM)
RYnE
not used
RXnE
not used
RYnF
Command code execution request
RXnF
Command code execution complete
RY(n+1)0
RX(n+1)0
RY(n+1)1
RX(n+1)1
RY(n+1)2
RX(n+1)2
RY(n+1)3
Reserved
RX(n+1)3
Reserved
RY(n+1)4
RX(n+1)4
RY(n+1)5
RX(n+1)5
RY(n+1)6
RX(n+1)6
RY(n+1)7
RX(n+1)7
RY(n+1)8
Initial data processing complete flag
RX(n+1)8
Initial data processing request flag
RY(n+1)9
Initial data setting request flag
RX(n+1)9
Initial data setting complete flag
RY(n+1)A
Error reset request flag
RX(n+1)A
Error status flag
RY(n+1)B
Vacancy
RX(n+1)B
Remote ready
RY(n+1)C
Reserved
RX(n+1)C
Reserved
RY(n+1)D
RX(n+1)D
RY(n+1)E
(Reserved: QnA)
RX(n+1)E
(Reserved: QnA)
RY(n+1)F
RX(n+1)F
Register word structure
Master -> Remote
Remote -> Master
Device No. Description
Device No. Description
RWwm
Monitor Code
RWrm
Monitor value
RWwm+1
Set Frequency
RWrm+1
Actual frequency
RWwm+2
Command code
RWrm+2
Reply Code
RWwm+3
Written data
RWrm+3
Read Data
Table 4-1
CC-Link Profile CBL
CC-Link profile for
inverters
All manuals and user guides at all-guides.com
all-guides.com
Содержание Simovert Masterdrive FANC-SB
Страница 8: ...All manuals and user guides at all guides com ...
Страница 14: ...All manuals and user guides at all guides com ...
Страница 48: ...All manuals and user guides at all guides com ...
Страница 58: ...All manuals and user guides at all guides com ...
Страница 70: ...All manuals and user guides at all guides com ...
Страница 72: ...All manuals and user guides at all guides com ...