03.99
Start-up of the CBL
Siemens AG
6SE7087-6NX84-0GB0
SIMOVERT MASTERDRIVES
Operating Instructions
5-9
The actual-value process data (PZDi, i = 1 to 16) are assigned to the
corresponding status words and actual values by means of the indexed
parameter P734.i (CB/TB actual values). Each index stands for an item
of process data.
Contents
Parameter
VC
MC
Meaning
Actual-value channel
connecting actual-values of converter to CBL transmit channel
(ACT VALUE: PZD1...16)
P734.1
0032
Mandatory: statusword 1
P734.2
0148
0151
Mandatory: actual value frequency
P734.3
0022
Mandatory: actual value output current
P734.4
0033
Mandatory: statusword 2
P734.5
0021
0189
Mandatory: actual value output voltage
P734.6
0070
Mandatory: setpoint frequency
P734.7
0148
0151
Mandatory: actual value rotation
P734.8
0024
Mandatory: actual value torque
P734.9
xxxx
Optional: Optional monitoring value 1
P734.10
xxxx
Optional: Optional monitoring value 2
P734.11
xxxx
Optional: Optional monitoring value 3
P734.12
xxxx
Optional: Optional monitoring value 4
P734.13
xxxx
Optional: Optional monitoring value 5
P734.14
xxxx
Optional: Optional monitoring value 6
P734.15
xxxx
Optional: Optional monitoring value 7
P734.16
xxxx
Optional: Optional monitoring value 8
CC-Link and the specified data structure for converters handle only 16-
bit values. For using 32-bit connectors refer to documentation of
converter.
Process data
softwiring of actual-
value channel
NOTE
All manuals and user guides at all-guides.com
Содержание Simovert Masterdrive FANC-SB
Страница 8: ...All manuals and user guides at all guides com ...
Страница 14: ...All manuals and user guides at all guides com ...
Страница 48: ...All manuals and user guides at all guides com ...
Страница 58: ...All manuals and user guides at all guides com ...
Страница 70: ...All manuals and user guides at all guides com ...
Страница 72: ...All manuals and user guides at all guides com ...