Communication via CC-Link
03.99
6SE7087-6NX84-0GB0
Siemens AG
4-8
Operating Instructions
SIMOVERT MASTERDRIVES
4.5 Monitoring
With the monitoring command you can get a selectable actual value of
the process. First select one process value by writing selection number
into register monitor code (RWwm). Second you activate monitoring
with monitor command (RYnC). While this bit is active and the CBL
acknowledges with bit monitoring (RXnC), you get actual values in
register monitoring value (RWrm). You can change the monitor code
during monitoring command is active. But attention, you don’t know at
which time you get actual values from the new selected process value!
Better you close the monitoring sequence, change the monitor code
and start a new sequence.
value a
value a
value b
value b
value b
value b
value a
monitor code a
monitor code b
RYnC
RWwm
RXnC
RWrm
Monitor
command
Monitor
code
Monitoring
Monitor
value
Fig. 4-5
Monitor command sequence
If you write an invalid value into monitor code you get 0000 in monitor
value.