03.99
Start-up of the CBL
Siemens AG
6SE7087-6NX84-0GB0
SIMOVERT MASTERDRIVES
Operating Instructions
5-7
Parameter
Contents
Meaning
Controlword 1
connecting CBL controlword 1 (REF VALUE: PZD1) to converter controlword 1
P554
3100
Mandatory: RUN/STOP
P555
1)
3101
Mandatory: MRS function
P565
3107
Mandatory: reset error flag
P568
3108
Mandatory: JOG mode
2)
P569
3109
Mandatory: JOG mode
2)
P571
3111
Mandatory: STF (Forward)
P572
3112
Mandatory: STR (Reverse)
1) use alternativly P555, P556 or P557 (AND function)
2) check P448 and P449 for JOG speed!
After power-up till data transmission between PLC cpu and CBL the
alarm message A035 will occur and will be displayed (control bits 11
and 12 equals 0!). The duration depends on the converter type and the
configuration (tech board plugged?) and takes some seconds. After
starting data transmission via CC-Link to PLC cpu the alarm will be
automatically cleared.
Parameter
Contents
Meaning
Controlword 2
connecting CBL controlword 2 (REF VALUE: PZD4) to converter controlword 2
P576
3400
Mandatory: RT function
P577
3401
Mandatory: RT function
P580
3404
Mandatory: RL, RM, RH
P581
3405
Mandatory: RL, RM, RH
P???
3411
Optional: Optionflag F27
P???
3412
Optional: Optionflag F28
P???
3413
Optional: Optionflag F29
Process data
softwiring of receive
channel
NOTE
All manuals and user guides at all-guides.com
Содержание Simovert Masterdrive FANC-SB
Страница 8: ...All manuals and user guides at all guides com ...
Страница 14: ...All manuals and user guides at all guides com ...
Страница 48: ...All manuals and user guides at all guides com ...
Страница 58: ...All manuals and user guides at all guides com ...
Страница 70: ...All manuals and user guides at all guides com ...
Страница 72: ...All manuals and user guides at all guides com ...