9.3
Ambient conditions
Climatic conditions
Temperature
Tested according to IEC 60068-2-1, IEC 60068-2-2, IEC 60068‑2‑14
- During operation
Standard rail mounting (preferred mounting position):
Operation with CFast card and/or SSD:
● With max. 1 expansion card
(max. load 10 W): 0 to +40° C
● With max. 1 expansion card
(max. load 10 W) in RAL
2
: 0 to +50° C
1
Operation with CFast card:
● Without expansion cards in RAL
2
: 0 to +55° C
1
Vertical mounting:
Operation with CFast card and/or SSD:
● Without expansion cards: 0 to +40° C
Operation with SSD:
● With max. 1 expansion card
(max. load 10 W) in RAL
2
: 0 to +45° C
1
Operation with CFast card:
● Without expansion cards
in RAL
2
: 0 to +50° C
1
● With max. 1 expansion card
(max. load 10 W): 0 to +40° C
● With max. 1 expansion card
(max. load 10 W) in RAL
2
: 0 to +50° C
1
- During storage/shipping
-40 °C to +70 °C (for devices with CFast or SSD)
- Gradient
Operating mode: Max. 10° C/h; Storage: 20° C/h; no condensation
Relative humidity
- During operation
- During storage/shipping
Tested according to IEC 60068-2-78, IEC 60068-2-30
5% to 80% at 25° C (no condensation)
5% to 95% at 25° C (no condensation)
Air pressure
- During operation
- During storage/shipping
1080 to 795 hPa
(corresponds to an altitude of -1000 m to 2000 m)
1080 to 660 hPa
(corresponds to an altitude of -1000 m to 3500 m)
1
For P320-4 S you must set "Turbo Mode Level" to "Temperature optimized" in the "Power" menu,
selection "Advanced CPU Control", of the BIOS Setup; otherwise you have to reduce the maximum
ambient temperature by 5 °C.
2
RAL = Restricted Access Location
Installation of device in operating facilities with restricted access, for example, a locked control cabinet.
Technical data
9.3 Ambient conditions
SIMOTION P320-4 E / P320-4 S
136
Manual, 03/2018, A5E36004933B
Содержание SIMOTION P320-4 E
Страница 10: ...Table of contents SIMOTION P320 4 E P320 4 S 10 Manual 03 2018 A5E36004933B ...
Страница 48: ...Industrial security 2 4 Product specific measures SIMOTION P320 4 E P320 4 S 48 Manual 03 2018 A5E36004933B ...
Страница 76: ...Description 3 3 HMI and SIMOTION SCOUT SIMOTION P320 4 E P320 4 S 76 Manual 03 2018 A5E36004933B ...
Страница 132: ...Troubleshooting FAQs 8 2 Hotplug Enabled BIOS settings SIMOTION P320 4 E P320 4 S 132 Manual 03 2018 A5E36004933B ...
Страница 154: ...Spare parts 11 1 Available spare parts for SIMOTION P320 4 SIMOTION P320 4 E P320 4 S 154 Manual 03 2018 A5E36004933B ...
Страница 156: ...Standards and approvals A 1 General rules SIMOTION P320 4 E P320 4 S 156 Manual 03 2018 A5E36004933B ...
Страница 166: ...Index SIMOTION P320 4 E P320 4 S 166 Manual 03 2018 A5E36004933B ...