Technical Specifications
A.2 Transmission Rates
Point-to-point connection CP 440 Installation and Parameter Assignment
Manual, 09/2007, A5E00057742-03
141
A.2
Transmission Rates
Transmission Rates
The tables below indicate the transmission times required depending on the transmission
protocol selected.
Two S7-400s each with a CPU 416 (6ES7 416-2XK02-0AB0) and a CP 440 were used to
measure the times. A SEND_440 FB was programmed in the user program of the active
CPU, and a RECV_440 FB was programmed in the user program of the passive CPU. The
time that elapsed between the initiation and completion of the request was measured.
ASCII Driver
Transmission times with the ASCII driver:
Table A-4
Transmission Times with the ASCII Driver in ms
Baud rate (bd)
User data
115200 76800
57600
38400
19200 9600 4800 2400 1200
600
300
1 bytes
1,5
2
2
2
3
4
8
15
29
55
110
10 bytes
2
2
3
5
8
14
28
56
111
220
440
20 bytes
4
5
6
8
14
26
52
102
202
404
807
50 bytes
6
9
12
17
32
60
120
240
478
952
1906
100 bytes
12
17
22
32
61
118
236
470
936
1872
3740
200 bytes
22
32
41
59
117
230
460
920
1835
3668
7330
3964(R) Procedure
Transmission times with the 3964(R) procedure:
Table A-5
Transmission Times with the 3964(R) Procedure in ms
Baud rate (bd)
User data
115200 76800 57600 38400 19200 9600 4800
2400 1200 600
300
1 bytes
4
4
5
7
9
11
20
35
68
134
264
10 bytes
5
5
7
8
14
22
40
77
150
296
594
20 bytes
6
7
8
10
20
33
64
122
242
484
960
50 bytes
9
11
14
20
36
68
132
260
518
1032
2060
100 bytes
14
19
24
34
64
126
248
490
976
1949
3894
200 bytes
24
34
44
64
118
240
476
948
1894 3780
7558
长沙工控帮教育科技有限公司