Point-to-point connection CP 440 Installation and Parameter Assignment
Manual, 09/2007, A5E00057742-03
13
Product Description
1
1.1
Uses of the CP 440
Applications
The CP 440 communication processor enables you to exchange data between automation
devices or computers by means of a point-to-point connection. The CP 440 is designed to
transfer short, fast frames.
The following are typically connected to it:
●
Scanners, barcode readers
●
Sensors
●
Weighing scales
Functionality of the CP 440
The CP 440 communication processor provides the following functionality:
●
An integrated MPI (Multipoint) X27 (RS422/485) interface
●
A maximum transmission length of 400 bytes (Page 86)
●
A transmission rate of up to 115.2 kbps, full-duplex
●
Integration of the most important transmission protocols in the module firmware
–
ASCII driver
–
3964(R) Procedure
●
Customization of the transmission protocols by means of parameter assignment with the
CP 440: Point-to-Point Communication, Parameter Assignment interface
Uses of the CP 440
The CP 440 communication processor allows point-to-point communication with
SIMATIC modules and with non-Siemens products.