Diagnostics with the CP 440
8.3 Diagnostics Messages of the Function Blocks
Point-to-point connection CP 440 Installation and Parameter Assignment
124
Manual, 09/2007, A5E00057742-03
Event Class 30
Event class 30 contains error messages which might occur during communication between
the CP 440 and the CPU via the S7 backplane bus.
The table below describes event class 30.
Table 8-3
Event Class 30
Event Class 30 (1EH): "Error during communication between CP and CPU"
Event no.
Event
Further Information/Remedy
(1E)0DH
•
Job aborted due to a cold restart, warm restart or
reset
•
Module firmware does not exist
•
Repeat the job.
•
Check whether the module is inserted.
(1E)0EH
Static error when the RD_RED SFC was called.
Return value RET_VAL of SFC is available for
evaluation in SFCERR variable in instance DB.
Load SFCERR variable from instance DB.
(1E)0FH
Static error when the WR_REC SFC was called.
Return value RET_VAL of SFC is available for
evaluation in SFCERR variable in instance DB.
Load SFCERR variable from instance DB.
(1E)41H
Number of bytes set in LEN parameter of FBs illegal. Keep to the value range of 1 to 400 bytes (Page
Calling the SFCERR variable
You can obtain more information on errors 14 (1E0EH) and 15 (1E0FH) in event class 30 by
means of the SFCERR variable.
You can load the SFCERR variable from the instance DB belonging to the corresponding
function block.
The error messages entered in the SFCERR variable are described in the section on the
system functions SFC 58 "WR_REC" and SFC 59 "RD_REC" in the
System Software for
S7-300/400, System and Standard Functions reference manual.