Diagnostics with the CP 440
8.3 Diagnostics Messages of the Function Blocks
Point-to-point connection CP 440 Installation and Parameter Assignment
120
Manual, 09/2007, A5E00057742-03
Event Class 7 (07H): "Send error"
Event no.
Event
To correct or avoid errors
(07)05H
With 3964(R) only:
Negative acknowledgment during sending
Check if the partner is also showing an error,
possibly because not all transmission data has
arrived (e.g. due to a break in the send line) or due
to serious faults or because the partner device has
malfunctioned. Identify the malfunction, possibly by
using an interface test device switched into the
transmission line.
(07)06H
With 3964(R) only:
Error at end of connection:
•
Partner rejected message frame at end of
connection with NAK or a random string
(except for DLE), or
•
Acknowledgment code (DLE) received too
early.
Check whether the partner is also showing an error,
possibly because not all transmission data has
arrived (e.g. due to break on line) or due to serious
faults or because the partner device has
malfunctioned. Identify the malfunction, possibly by
using an interface test device switched into the
transmission line.
(07)07H
With 3964(R) only:
Acknowledgment delay time exceeded at end of
connection or response monitoring time exceeded
after send message frame:
After connection release with DLE ETX, no
response received from partner within
acknowledgment delay time.
Partner device faulty or too slow. Identify the
malfunction, possibly by using an interface test
device switched into the transmission line.
(07)08H
For ASCII driver only:
The waiting time for XON or CTS = ON has expired
The communication partner has a fault, is too slow or
is switched off-line. Check the communication
partner or, if necessary, change the parameters.
(07)09H
With 3964(R) only:
Connection setup not possible. Number of
permitted setup attempts exceeded.
Check the interface cable or the transmission
parameters.
Also check that receive function between CPU and
CP is correctly configured at the partner device.
(07)0AH
With 3964(R) only:
The data could not be transmitted. The permitted
number of transfer attempts was exceeded.
Check the interface cable or the transmission
parameters.
(07)0BH
With 3964(R) only:
Initialization conflict cannot be solved because
both partners have high priority.
Change the parameter assignment.
(07)0CH
With 3964(R) only:
Initialization conflict cannot be solved because
both partners have low priority.
Change the parameter assignment.