Point-to-point connection CP 440 Installation and Parameter Assignment
Manual, 09/2007, A5E00057742-03
137
Technical Specifications
A
A.1
Technical Specifications of the CP 440
General technical data
The following table contains the general technical specifications of the CP 440.
You will find further general technical specifications of the SIMATIC S7-400 in the
S7-400
and M7-400 Programmable Controllers, Module Specifications reference manual, "General
Technical Specifications", and the S7-400 and M7-400 Programmable Controllers, Module
Specifications manual.
●
Electronic compatibility
●
Shipping and storage conditions
●
Mechanical and climatic environmental conditions
●
Information on insulation testing, safety class and degrees of protection
●
Certification
Technical Specifications
Dimensions W x H x D
29 x 290 x 210 mm
Weight
0,3 kg
Current consumption from the backplane bus
Max. 0.36 A at 5 V, typically 0.33 A at 5 V
Power loss
Max. 1.9 W, typically 1.7 W
Display elements
LEDs for transmitting (TXD), receiving (RXD)
and interface fault (FAULT) Group alarm LEDs
for internal fault (INTF) and external fault
(EXTF)
Diagnostic functions
•
Indicators for internal and external faults
•
Diagnostic information dump
•
Yes, 2 red LEDs
•
Yes
Supplied protocol drivers
•
ASCII driver
•
3964(R) Procedure
Transmission rates with 3964(R) protocol
300, 600, 1200, 2400, 4800, 9600, 19200,
38400, 57600, 76800, 115200 bps
Transmission rates with ASCII driver
300, 600, 1200, 2400, 4800, 9600, 19200,
38400, 57600, 76800, 115200 bps
长沙工控帮教育科技有限公司