Programming options
5
5.1
Easy to configure the hardware devices
You create the device configuration for your PLC by adding a CPU and additional modules to
your project.
①
Communications module (CM): Up to 3, inserted in slots 101, 102, and 103
②
CPU: Slot 1
③
Ethernet port of CPU
④
Signal board (SB): up to 1, inserted in the CPU
⑤
Signal module (SM) for digital or analog I/O: up to 8, inserted in slots 2 through 9
CPU 1214C allows 8, CPU 1212C allows 2, CPU 1211C does not allow any
To create the device configuration, add
a device to your project.
•
In the Portal view, select "Devices &
Networks" and click "Add device".
•
In the Project view, under the
project name, double-click "Add new
device".