Configuring
5.2 Configuration via PROFINET IO (STEP 7)
SIMATIC RF360R
Configuration Manual, 03/2022, C79000-G8976-C629-02
31
With the "RFID Communiction_1" submodule, configurations can be transferred from or to
the connected communications module, and a status query can be performed via the
communications module.
Table 5- 4
Parameters of the parameter group "Module parameters > General parameters" of the submodules (connected
devices)
Parameter
Parameter value
Default value
Description
User mode
Ident profile/RFID
standard profile
FB 45
Ident profile/RFID
standard profile
With this parameter, you select the block:
•
Ident profile/RFID standard profile:
Single tag / multitag mode. The program
block for the Ident profile is used in the
controller.
•
FB 45:
Single tag mode. FB 45 is used in the
controller.
Only in connection with an S7-300
controller.
Diagnostic
interrupt
None
Hard errors
Hard/soft errors
None
With this parameter, you determine the extent
to which the reader-related diagnostic interrupt
messages are to be reported.
•
None:
No alarms are generated.
•
Hard errors:
Critical hardware errors/faults are reported
by the S7 diagnostics.
•
Hard/soft errors:
Critical hardware faults and errors occurring
when processing commands are reported by
the S7 diagnostics.
Description of block commands
You can find a description of the block-specific commands in the respective block manuals:
•
RFID standard profile; standard function for RFID systems
•
Ident profile and Ident blocks, standard function for Ident systems