background image

Service and maintenance 

 

7.2 Memory reset - ACL 

 

CP 343-1 

58

 

Manual, 12/2018, 

C79000−G8976−C201

-08 

 

Reset to factory settings 

 

In STEP 7 V5.5 with the menu command "PLC" > "Edit Ethernet Node..." > Select CP 

> "OK" > "Reset to Factory Defaults"

 

 

In STEP 7 special diagnostics with the "Operating Mode" > "Reset to Factory Settings" 

menu command 

 

In STEP 

7 Professional V11 with "Online > Online & Diagnostics > Functions > Reset 

to Factory Settings" 

Behavior after a memory reset 

The CPU in the S7 station does not recognize that the CP memory was reset. The CP 

therefore changes to the "Stopped (STOP) with error" state (see LEDs (Page 31))
The configuration data must then be reloaded. 
If the configuration data is stored on the CPU, you can start a download by cycling power. 

7.2

 

Memory reset - ACL 

 

 

Note 
After the memory reset, the previously configured IP-ACL (IP Access Control List) remains 

active. 

 

7.3

 

Loading new firmware 

Options for a firmware update 

The following alternative methods can be used to download new firmware to a SIMATIC NET 

CP: 

 

Using the firmware loader supplied with STEP 7 
Requirement for downloading: 

 

To download firmware, you require an Industrial Ethernet CP module in the PG/PC 

(for example, CP 

1613) or a normal Ethernet module with the "Softnet" 

software 

package. 

 

The S7ONLINE interface must be set to the "ISO - Industrial Ethernet" protocol. It is 

not possible to download using TCP/IP (and therefore not to other networks). 

Always run the download using the active MAC address of the CP! 

Содержание SIMATIC NET CP 343-1

Страница 1: ... ___________________ ___________________ SIMATIC NET S7 300 Industrial Ethernet PROFINET CP 343 1 Manual Manual Part B 12 2018 C79000 G8976 C201 08 Preface Properties services 1 Performance data 2 Requirements for use 3 LEDs 4 Installation connecting up and commissioning 5 Configuration and operation 6 Service and maintenance 7 Technical specifications 8 Approvals A References B ...

Страница 2: ...e operated only by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING...

Страница 3: ...X placeholder for hardware product version Figure 1 CP 343 1 Validity and product names This description contains information on the following product CP 343 1 Article number 6GK7343 1EX30 0XE0 Hardware product version 7 Firmware version V3 0 Communications processor for SIMATIC S7 300 C7 300 und SINUMERIK 840D power line CP 343 1 Article number 6AG1343 1EX30 7XE0 Hardware product version 7 Firmwa...

Страница 4: ...lt MAC address The MAC address is printed on the housing Address label Unique MAC address for the CP The CP is supplied with total of 3 default MAC addresses with the following assignment PROFINET interface One MAC address for each of the 2 Ethernet ports of the PROFINET interface The MAC addresses of the Ethernet ports are required only for detection and evaluation of neighborhood and topology re...

Страница 5: ...et pages of Siemens Automation Customer Support under the following entry ID Link http support automation siemens com WW view en 24485272 CP documentation in the Manual Collection order no A5E00069051 The SIMATIC NET Manual Collection DVD contains the device manuals and descriptions of all SIMATIC NET products current at the time it was created It is updated at regular intervals Version History Cu...

Страница 6: ...y measures e g firewalls and or network segmentation are in place For additional information on industrial security measures that may be implemented please visit Link http www siemens com industrialsecurity Siemens products and solutions undergo continuous development to make them more secure Siemens strongly recommends that product updates are applied as soon as they are available and that the la...

Страница 7: ...quipment Do not dispose of the product at public disposal sites For environmentally friendly recycling and the disposal of your old device contact a certified disposal company for electronic scrap or your Siemens contact Keep to the local regulations You will find information on returning the product on the Internet pages of Siemens Industry Online Support Link https support industry siemens com c...

Страница 8: ...Preface CP 343 1 8 Manual 12 2018 C79000 G8976 C201 08 ...

Страница 9: ...data of the integrated switch 23 3 Requirements for use 25 3 1 Operation in control device families 25 3 2 Project engineering 28 3 3 Programming 29 4 LEDs 31 5 Installation connecting up and commissioning 35 5 1 Important notes on using the device 35 5 2 Installing the CP connecting power and ground 37 5 3 Connecting the CP to Ethernet 40 6 Configuration and operation 43 6 1 Security recommendati...

Страница 10: ...ps on standard IT interfaces preventing unauthorized access 54 6 12 Programmed communication connections 55 6 12 1 Programmed communication connections with FB55 IP_CONFIG 55 6 12 2 Programmed communications connections assigning parameters to the ports 55 6 12 3 IP access protection with programmed communication connections 55 6 13 Permitted length of ICMP packets 56 6 14 Downtime if an S7 connec...

Страница 11: ... the features listed below the following STEP 7 version is necessary STEP 7 V5 5 Service Pack 2 Hotfix 1 HSP 1057 With STEP 7 Professional V11 0 SP2 only the functions of firmware version V2 2 of the CP can be configured Functional enhancements of the EX30 from firmware version V2 6 to V3 0 can be used with STEP 7 V5 5 The following new functions can be used with the module with firmware version 3...

Страница 12: ... modules You will find an overview of the earlier firmware versions and predecessor modules in the version history of the Industrial Ethernet CPs on the Internet pages of Siemens Automation Customer Support under the following entry ID 56699406 http support automation siemens com WW view en 56699406 You will find information about the characteristics of the individual firmware versions on the Inte...

Страница 13: ... BSEND FB 12 BRCV FB 13 PUT FB 14 GET FB 15 USEND FB 8 URCV FB 9 C_CNTRL FC 62 Server for data exchange on S7 connections configured at one end only without communication blocks on the S7300 C7300 station Open communication services with the following functions SEND RECEIVE interface over ISO transport connections ISOonTCP TCP and UDP connections UDP frame buffering on the CP can be disabled durin...

Страница 14: ...he CPU is optional Accuracy approx 1 second Addressing using a factoryset MAC address The CP can be reached via the default or configured MAC address to allow an IP address to be assigned SNMP agent The CP supports data queries over SNMP in version V1 Simple Network Management Protocol It delivers the content of certain MIB objects according to the MIB II standard LLDP MIB Automation System MIB an...

Страница 15: ...ping function You can find out which connection types are set up for the SEND RECEIVE interface 1 5 The CP as Web server Enabling the Web server function To use the Web server functionality of the CP enable the relevant option in STEP 7 in the module properties Web parameter group This enables port 80 of the CP If you no longer require the functions deactivate the function The Web server function ...

Страница 16: ...s to the CP and further information about Web diagnostics can be found in the general Part A of this manual Web browser To access the HTML pages on the CP you require a Web browser The following Web browsers are suitable for communication with the CP other browsers also possible Internet Explorer recommended version as of 7 0 Chrome recommended version as of 12 0 Opera recommended version as of 9 ...

Страница 17: ... www siemens com automation pd http www siemens com automation pd 2 2 Number of possible Ethernet PROFINET connections Maximum number of parallel connections Table 2 1 Maximum number of parallel connections Characteristic Explanation values Permitted number of simultaneous connections in total over Industrial Ethernet 32 maximum Example of maximum load You can for example operate 16 S7 connections...

Страница 18: ...dustrial Ethernet in each case up to 16 operator control and monitoring functions HMI 16 S7 connections configured at one end 16 S7 connections configured at both ends The number depends on the CPU type being used the valid values can be found in 1 Page 71 You should still keep to the maximum number of Ethernet connec tions specified in the section Number of possible Ethernet PROFINET connections ...

Страница 19: ...und on the Internet at the following address 25209605 http support automation siemens com WW view en 25209605 2 4 Characteristic data of the SEND RECEIVE Interface The SEND RECEIVE interface provides access to communication over TCP ISOonTCP ISO transport and UDP connections The following characteristics are important Table 2 4 Characteristic data of the SEND RECEIVE interface Characteristic Expla...

Страница 20: ...alculation of the CPU cycle times OB1 for SEND RECEIVE connections Note Measurements of transmission and reaction times in Ethernet PROFIBUS and PROFINET networks for a series of configurations can be found on the Internet at the following address 25209605 http support automation siemens com WW view en 25209605 2 5 PROFINET IO characteristic data Possible modes with PROFINET IO In PROFINET IO the ...

Страница 21: ...ve a mes sage about lack of resources in the diagnostics buffer of the CP when downloading the configuration data The diagnostics addresses of the PROFINET IO devices cannot be used as an input on the IO controller The data area of the inputs is reduced by the diagnostics addresses used Configuration limits of the CP as a PROFINET IO device The CP supports the following maximum configuration as a ...

Страница 22: ... in HW Config or per slot used Table 2 8 Example of calculating the user data of the CP 343 1 as an IO device Bytes Explanation 548 Gross size of the frame 1 for the CP itself 1 for the Interface 2 for 2 ports 32 for the maximum number of pluggable modules 512 Net size of the user data By using fewer but larger modules the amount of user data can be increased Execution times of the FC blocks PNIO_...

Страница 23: ...s this packet only to the port via which the appropriate end node can be reached The switch monitors the age of the learned addresses Addresses that exceed the aging time are deleted The aging time is 5 minutes Ports can be deactivated individually The ports of the switch integrated in the CP can be deactivated individually in STEP 7 HW Config This can for example be used for service purposes To d...

Страница 24: ...Performance data 2 6 Characteristic data of the integrated switch CP 343 1 24 Manual 12 2018 C79000 G8976 C201 08 ...

Страница 25: ...at the time this manual went to print CPUs of the S7 300 or C7 control systems released later and not listed in the tables can also handle the range of functions described here Table 3 1 Use of the CP with S7 300 CPU Order number CPU 312 6ES7 312 1AD10 0AB0 6ES7 312 1AE13 0AB0 6ES7 312 1AE14 0AB0 CPU 312C 6ES7 312 5BD00 0AB0 6ES7 312 5BD01 0AB0 6ES7 312 5BE03 0AB0 CPU 312 IFM 6ES7 312 5AC02 0AB0 6...

Страница 26: ... 315 1AF03 0AB0 CPU 315 2 DP 6ES7 315 2AF03 0AB0 6ES7 315 2AF83 0AB0 6ES7 315 2AG10 0AB0 6ES7 315 2AH14 0AB0 CPU 315 2 PN DP 6ES7 315 2EG10 0AB0 6ES7 315 2EH13 0AB0 6ES7 315 2EH14 0AB0 CPU 315F 2 DP 6ES7 315 6FF00 0AB0 6ES7 315 6FF01 0AB0 6ES7 315 6FF04 0AB0 CPU 315F 2 PN DP 6ES7 315 2FH10 0AB0 6ES7 315 2FH13 0AB0 6ES7 315 2FJ14 0AB0 CPU 315T 2 DP 6ES7 315 6TG10 0AB0 6ES7 315 6TH13 0AB0 CPU 316 2 ...

Страница 27: ... 635 Key 6ES7 635 2EC01 0AE3 6ES7 635 2EC02 0AE3 C7 635 Touch 6ES7 635 2EB01 0AE3 6ES7 635 2EB02 0AE3 C7 636 Key 6ES7 636 2EC00 0AE3 C7 636 Touch 6ES7 636 2EB00 0AE3 Table 3 3 Using the CP with SINUMERIK 840D power line Equipment group with CPU type Order number NCU561 4 with PLC 314 2 DP 6FC5 356 0BB14 0AA0 NCU571 4 with PLC 314C 2 DP 6FC5 357 0BB14 0AA0 NCU572 4 with PLC 314C 2 DP 6FC5 357 0BB24...

Страница 28: ... automation siemens com WW view en 23183356 STEP 7 Professional V11 You will find the support package on the Internet at the following addresses 28919804 http support automation siemens com WW view en 28919804 or 10806075 http support automation siemens com WW view en 10806075 On the Internet page select the Entry list tab and the Download entry type Installation of the support package STEP 7 V5 5...

Страница 29: ... Program blocks For some communications services there are preprogrammed program blocks FCs FBs available as the interface in your STEP 7 user program Please note the documentation of the program blocks in the online help of STEP 7 or in the manual 10 Page 73 Note Current block versions We recommend that you always use the latest block versions for all module types You will find information on the...

Страница 30: ...Requirements for use 3 3 Programming CP 343 1 30 Manual 12 2018 C79000 G8976 C201 08 ...

Страница 31: ...V 5 VDC power supply via the backplane bus green OK RX TX Acyclic data traffic for example SEND RECEIVE not relevant for PROFINET IO data RUN RUN mode STOP STOP mode X1P1 Link status activity of Ethernet port 1 X1P2 Link status activity of Ethernet port 2 MAINT Maintenance required note evaluate diagnostics buffer Legend for the following LED tables Symbol Meaning ON OFF Flashing any LEDs for disp...

Страница 32: ...ROFINET IO controller The CP configured as an I O controller has recog nized at least 1 IO device as being disrupted Running RUN with error Possible causes Event display in conjunction with the MRP func tion The CP diagnostics buffer provides detailed information Extended port diagnostics reports an error Ex amples Current port setting transmission medium duplex does not correspond to the configur...

Страница 33: ...strial Ethernet Existing connection via port to Industrial Ethernet LINK status LED flashes yellow constant light green Port sending receiving over Industrial Ethernet or PROFINET IO Note All received sent frames are signaled for each specific port including those simply forwarded by the switch There is permanent data transfer at the port via Industrial Ethernet e g PROFINET IO Module identificati...

Страница 34: ...LEDs CP 343 1 34 Manual 12 2018 C79000 G8976 C201 08 ...

Страница 35: ...s not apply to 100 V 240 V devices This means that only SELV LPS complying with IEC 60950 1 EN 60950 1 VDE 0805 1 must be connected to the power supply terminals The power supply unit for the equipment power supply must comply with NEC Class 2 as described by the National Electrical Code r ANSI NFPA 70 There is an additional requirement if devices are operated with a redundant power supply If the ...

Страница 36: ...zardous locations only WARNING Restricted area of application This equipment is suitable for use in Class I Zone 2 Group IIC or non hazardous locations only WARNING LAN attachment A LAN or LAN segment with the attachments belonging to it should be within a single low voltage supply system and within a single building Make sure that the LAN is in an of type A environment according to IEEE 802 3 or ...

Страница 37: ...ture range of the selected cable must be suitable for the temperatures actually measured WARNING Protection against transient voltage surges Provisions shall be made to prevent the rated voltage from being exceeded by transient voltage surges of more than 40 This criterion is fulfilled if supplies are derived from SELV Safety Extra Low Voltage only 5 2 Installing the CP connecting power and ground...

Страница 38: ...ng and chassis ground concept in the SIMATIC S7 installation guides see SIMATIC S7 Programmable Controller S7300 Installation and Hardware Installation Manual 12 Page 74 Behind the hinged panel on the left of the device you will see a slider with which you can connect or disconnect the chassis ground of the 24V power supply with reference ground Slider pushed in Chassis ground and reference ground...

Страница 39: ...via the enclosed bus connector to the backplane bus 3 Connect the CP to the power supply Follow the steps as described in detail in 12 Page 74 when wiring between the power supply and the CPU NOTICE Same power supply The CPU CP and IM if one exists must be connected to the same power supply Only wire up the S7300 C7300 with the power switched off 4 Connect the CP to Industrial Ethernet An Ethernet...

Страница 40: ...lowing options are available The LED displays on the CP Hardware diagnostics and troubleshooting with STEP 7 Communication diagnostics with STEP 7 NCM Diagnostics Static information using HW Config Web diagnostics If applicable evaluation of the alarm block FB 54 in the user program Queries via SNMP 5 3 Connecting the CP to Ethernet Connecting interface X1 to Industrial Ethernet 1 Connect the CP t...

Страница 41: ...ollowing points Manual configuration If a port is set to manual configuration and autonegotiation is disabled the autocrossing mechanism is also disabled for this port Which cable you need to use depends on the partner device network component or end device In the factory the ports are set for automatic configuration For more information refer to section Network settings Page 47 Connecting switche...

Страница 42: ...Installation connecting up and commissioning 5 3 Connecting the CP to Ethernet CP 343 1 42 Manual 12 2018 C79000 G8976 C201 08 ...

Страница 43: ...ware and use them Check regularly for new features on the Siemens Internet pages Here you will find information on industrial security Link http www siemens com industrialsecurity Here you will find information on security in industrial communication Link http w3 siemens com mcms industrial communication en ie industrial ethernet security Seiten industrial security aspx You will find a publication...

Страница 44: ...nt of passwords Regularly update the passwords to increase security Only use passwords with a high password strength Avoid weak passwords for example password1 123456789 or similar Make sure that all passwords are protected and inaccessible to unauthorized personnel See also the preceding section for information on this Do not use one password for different users and systems Protocols Secure and n...

Страница 45: ...g in Open with block call The port is only opened when a suitable program block is called Authentication Specifies whether or not the protocol authenticates the communications partner during access Protocol function Port number pro tocol Default of the port Port status Authentication S7 and online connections 102 TCP Open Open after configuration No HTTP 80 TCP Closed Open after configuration No S...

Страница 46: ...and then changes to RUN mode Change from RUN to STOP The CP changes to STOP transitional phase with LED display Stopping RUN STOP Established connections of the open communications services see also section Communication services Page 12 are terminated The following functions are disabled PROFINET IO Time of day synchronization The following functions remain enabled Downloading the configuration d...

Страница 47: ... no longer effective If on the other hand the communication partner works with autonegotiation no communication will be established Only use manual configuration when the communication partner works with the same manually set configuration Autocrossing mechanism The automatic setting also includes an autocrossing mechanism With autocrossing you can connect network components and end devices using ...

Страница 48: ...tablished Example If the CP is set to 100 Mbps full duplex a CP connected as partner will set itself to 100 Mbps half duplex Reason Due to the fixed setting no autonegotiation response is possible the connected partner recognizes the 100 Mbps with autosensing but nevertheless remains in half duplex Recommendation Change individual network settings only over MPI If you modify the LAN settings in th...

Страница 49: ...ROR and STATUS parameters must be evaluated in FC11 FC12 6 6 PROFINET IO 6 6 1 How PROFINET IO devices start up in a large configuration When operating the module with a large configuration up to 32 communications connections and up to 32 PROFINET IO devices it may take several minutes when the station starts up before all PROFINET IO devices have received configuration data from the PROFINET IO c...

Страница 50: ... configuration 6 7 1 Detection of double IP addressing in the network To save you timeconsuming troubleshooting in the network the CP detects double addressing in the network The reaction of the CP when double addressing is detected varies as follows CP during startup When the CP starts up following a power down or after assigning an Ethernet address a query for its own IP address is sent into the...

Страница 51: ...using DHCP any S7 connections you may have configured will not work Reason The configured IP address is replaced during operation by the address obtained with DHCP 6 7 4 IP access protection using the IP access control list with a PROFINET IO device Note the following behavior if IP access protection is activated If the CP is configured as a PROFINET IO device you will need to enter the IP address...

Страница 52: ...g networks To transmit data SNMP uses the connectionless UDP protocol The information on the properties of SNMPcompliant devices is entered in MIB files MIB Management Information Base The CP supports data queries via SNMP in Version 1 It returns the contents of certain MIB objects according to the MIB II standard LLDP MIB Automation System MIB and MRP Monitoring MIB MIB file and SNMP profile file...

Страница 53: ... MIB Exceptions restrictions Write access is permitted only for the following MIB objects of the system group sysContact sysLocation sysName A set sysName is sent as the host name using DHCP option 12 to the DHCP server to register with a DNS server For all other MIB objects MIB object groups only read access is possible for security reasons Traps are not supported by the CP Interfaces MIB group T...

Страница 54: ... range of parameter assignment and diagnostics functions for example Web servers network management are available using open protocols and interfaces The possibility of unauthorized misuse of these open protocols and interfaces by third parties for example to manipulate data cannot be entirely excluded When using the functions listed above and these open interfaces and protocols for example SNMP H...

Страница 55: ...RT parameter The port can be specified as an option when the connection is established passively 6 12 3 IP access protection with programmed communication connections In principle it is possible to set up communications connections using program block IP_CONFIG FB55 by programming and at the same time by configuring IP access protection When configuring specified connections active endpoints in ST...

Страница 56: ...nse is intentional and improves the robustness of the CP in an industrial environment 6 14 Downtime if an S7 connection aborts Note Downtime if an S7 connection aborts If an S7 connection is aborted for example failure of the connection partner it can take up to 40 s before the connection abort is recognized in the block Block processing is aborted and the block resource is available again This ap...

Страница 57: ...e IP address The retentive parameters include IP address subnet mask and if applicable router address LAN settings Reset to factory settings After resetting the CP only contains the default MAC address as shipped Note The functions for memory reset and resetting to defaults described here do not change the configuration data on the CPU If you subsequently upload the configuration data from the CPU...

Страница 58: ... be reloaded If the configuration data is stored on the CPU you can start a download by cycling power 7 2 Memory reset ACL Note After the memory reset the previously configured IP ACL IP Access Control List remains active 7 3 Loading new firmware Options for a firmware update The following alternative methods can be used to download new firmware to a SIMATIC NET CP Using the firmware loader suppli...

Страница 59: ...n such cases this can lead to an interruption of the firmware download The firmware loader then signals a timeout or negative response from the module being loaded In this case turn the station off and on again and repeat the download 7 4 Replacing a module Note Recommendation to reset address data if the use of the CP is changed The following data is stored permanently on the CP A configured MAC ...

Страница 60: ...e replacement This is necessary when new characteristics that were not available in the previously used module are required 7 4 2 Module replacement upgrading Replacing a module The CP 343 1 6GK7 343 1EX30 0XE0 described here can be used as a replacement for the following predecessor products CP 343 1 6GK7 343 1EX10 0XE0 CP 343 1 6GK7 343 1EX11 0XE0 CP 343 1 6GK7 343 1EX20 0XE0 CP 343 1 6GK7 343 1...

Страница 61: ...visable to always use the current block versions If you use the module described here as replacement for the modules listed below the blocks listed following this list must be used Modules used 6GK7 343 1EX10 0XE0 6GK7 343 1EX11 0XE0 configured as 6GK7 343 1EX10 0XE0 Block versions to be used AG_SEND as of V4 2 AG_RECV as of V4 7 AG_LOCK as of V4 0 AG_UNLOCK as of V4 0 Note Always use the latest b...

Страница 62: ...e steps below 1 Replace the previously configured CP with the new module in STEP 7 HW Config You will find this in the hardware catalog 2 Expand your configuration to suit your needs for exam ple the connection configuration 3 Save compile and load the configuration data to the CPU or CP again Note Note the following information on the module types listed in the table above With the current CP not...

Страница 63: ... the IP configuration for the CP One option here is that the CP obtains the IP address from a DHCP server Note When replacing modules please remember that the factoryset MAC address of the new module is different from the previous module When the factoryset MAC address of the new module is sent to the DHCP server this will return either a different or possibly no IP address Ideally you should ther...

Страница 64: ...Service and maintenance 7 4 Replacing a module CP 343 1 64 Manual 12 2018 C79000 G8976 C201 08 ...

Страница 65: ...tion From external power supply 200 mA maximum From backplane bus 200 mA maximum Effective power loss 5 8 W Permitted ambient conditions Ambient temperature During operation with the rack in stalled horizontally 0 to 60 During operation with the rack in stalled vertically 0 to 40 During storage 40 to 70 During transportation 40 to 70 Relative humidity During operation 95 at 25 C no condensation Op...

Страница 66: ... information in the SIMATIC S7 300 Automation System Module Data see 12 Page 74 in the section General Technical Specifications on the topics listed below applies to the CP Electromagnetic compatibility Transportation storage conditions Mechanical and climatic environmental conditions Information on insulation checks protection class and degree of protection ...

Страница 67: ...onized European standards EN for programmable logic controllers which are published in the official documentation of the European Union EC Directive 2004 108 EEC Electromagnetic Compatibility EMC Directive Immunity EN 61000 6 2 2005 Emission EN 61000 6 4 A1 2007 2011 The device is designed for use in an industrial environment EC directive 94 9 EC Equipment and protective systems intended for use i...

Страница 68: ...rements EN 60079 15 Explosive atmospheres Part 15 Equipment protection by type of protection n Ex ec IIC T4 Gc Certificate IECEx DEK 18 0019X Applied standards EN 60079 0 Explosive atmospheres Part 0 Equipment General requirements EN 60079 7 Explosive Atmospheres Part 7 Equipment protection by increased safety e You can see the current versions of the standards in the IECEx certificate that you wi...

Страница 69: ... protection by increased safety e WARNING Installation guidelines The product meets the requirements if you keep to the following during installation and operation The notes in the section Installation connecting up and commissioning Page 35 The installation instructions in the document 12 Page 74 The current versions of the standards can be seen in the EU Declaration of Conformity see above The c...

Страница 70: ...l Equipment CSA C22 2 No 213 Hazardous Location APPROVED for Use in Cl 1 Div 2 GP A B C D T4A Ta 0 C 60 C Cl 1 Zone 2 GP IIC T4 Ta 0 C 60 C FM approval Factory Mutual Research FM Approval Standard Class Number 3611 APPROVED for Use in Class I Division 2 Group A B C D Temperature Class T4A Ta 0 C 60 C Class I Zone 2 Group IIC Temperature Class T4 Ta 0 C 60 C Notice for Australia C TICK AS NZS 2064 ...

Страница 71: ...Documentation on the Internet You will find SIMATIC NET manuals on the Internet pages of Siemens Automation Customer Support Link http support automation siemens com WW view en 10805878 Go to the required product group and make the following settings Entry list tab Entry type Manuals Operating Instructions Documentation from the STEP 7 installation Manuals that are included in the online documenta...

Страница 72: ...part of the online documentation in STEP 7 4 SIMATIC NET Commissioning PC Stations instructions and getting started Configuration manual Siemens AG SIMATIC NET Manual Collection On the Internet under following entry ID 13542666 http support automation siemens com WW view de 13542666 5 SIMATIC Configuring Hardware and Connections with STEP 7 Siemens AG Part of the documentation package STEP 7 Basic...

Страница 73: ... AG SIMATIC NET Manual Collection On the Internet under following entry ID Link https support industry siemens com cs ww en view 77376110 SIMATIC NET Industrial Communication with PG PC Volume 2 Interfaces Programming manual Siemens AG SIMATIC NET Manual Collection On the Internet under following entry ID Link https support industry siemens com cs ww en view 77378184 10 SIMATIC NET Program blocks ...

Страница 74: ...al AUTOHOTSPOT Automation system S7 400 M7 400 Installation Installation manual AUTOHOTSPOT Module Data Reference manual AUTOHOTSPOT B 5 For application and configuration of PROFINET IO 13 SIMATIC PROFINET System Description System manual Siemens AG SIMATIC NET Manual Collection On the Internet under following entry ID 19292127 http support automation siemens com WW view en 19292127 14 SIMATIC Fro...

Страница 75: ...com cs ww en view 84922825 B 7 SIMATIC and STEP 7 basics 17 SIMATIC Communication with SIMATIC system manual Siemens AG Entry ID 25074283 http support automation siemens com WW view en 25074283 18 Documentation package STEP 7 Basic Knowledge Working with STEP 7 Getting Started ID 18652511 Programming with STEP 7 ID 18652056 Configuring Hardware and Connections with STEP 7 ID 18652631 From S5 to S7...

Страница 76: ... 12 2018 C79000 G8976 C201 08 20 RFC 1006 ISO Transport Service on top of the TCP Version 3 Request For Comment http www ietf org http www ietf org 21 RFC 793 TCP http www ietf org http www ietf org 22 RFC 791 IP http www ietf org http www ietf org ...

Страница 77: ...nation 5 G Glossary 6 GSDML file 29 H Hazardous area 35 Hazardous areas according to ATEX 36 I IP configuration 5 M MAC address 4 59 Manual Collection 5 O Open communication services 5 P Ping 56 PROFIenergy 11 Programmed connections and IP configuration 5 Protection against transient voltage surges 37 R Recycling 7 Replacing components 36 S Safety extra low voltage 35 Safety notices 35 SIMATIC NET...

Страница 78: ...Index CP 343 1 78 Manual 12 2018 C79000 G8976 C201 08 ...

Отзывы: