Performance data
2.3 Characteristics of S7 communication
CP 343-1
18
Manual, 12/2018,
C79000−G8976−C201
-08
Also:
●
Further TCP connections for Web diagnostics
●
PROFINET IO
–
As PROFINET IO device:
1 PROFINET connection to a PROFINET IO controller
or
–
As shared device:
2 PROFINET connections to 2 PROFINET IO controllers
or
–
As PROFINET IO controller:
Max. 32 PROFINET connections to PROFINET IO devices
2.3
Characteristics of S7 communication
Number of connections
Table 2- 2
Number of connections for S7 communication
Characteristic
Explanation / values
Number of connections for S7 communication via
Industrial Ethernet.
in each case, up to
•
16 operator control and monitoring functions (HMI)
•
16 S7
connections configured at one end
•
16 S7 connections configured at both ends
The number depends on the CPU type being used; the valid values
can be found in /1/ (Page 71).
You should still keep to the maximum number of Ethernet conne
c-
tions specified in the section Number of possible Ethernet/PROFINET
connections (Page 17).
maxi
mum 16 resources
For each executed S7 communications function, a job resource is
required. If the CP has 16 job resources, then only 1 PUT or GET job
can be executed at one time on each of the 16 S7 connections. The
same applies to BSEND/BRECV and USEND/URECV jobs.
LAN interface - data field length generated by CP
per protocol data unit
•
sending
•
receiving
•
240 bytes / PDU
•
240 bytes / PDU
Содержание SIMATIC NET CP 343-1
Страница 8: ...Preface CP 343 1 8 Manual 12 2018 C79000 G8976 C201 08 ...
Страница 30: ...Requirements for use 3 3 Programming CP 343 1 30 Manual 12 2018 C79000 G8976 C201 08 ...
Страница 34: ...LEDs CP 343 1 34 Manual 12 2018 C79000 G8976 C201 08 ...
Страница 64: ...Service and maintenance 7 4 Replacing a module CP 343 1 64 Manual 12 2018 C79000 G8976 C201 08 ...
Страница 78: ...Index CP 343 1 78 Manual 12 2018 C79000 G8976 C201 08 ...