Error messages and troubleshooting
5.2 Error messages
FC 45
5-10
Function manual, Release 03/2006 , J31069-D0167-U001-A2-7618
error_BUS
Table 5-4
Error variable "error_BUS"
Error code
(W#16#...)
Description
800A
ASM is not ready (temporary message).
•
This message is given to a user who is not using the FC 45 and is continuously
polling the ASMs acyclicaly.
8x7F
Internal error on parameter x. Cannot be remedied by the user.
8x22
8x23
Area length error on reading parameter.
Area length error on writing parameter.
This error code indicates that parameter x is partially or completely outside the
operand area or the length of a bit array for an ANY parameter is not divisible by 8.
8x24
8x25
Area error on reading parameter.
Area error on writing parameter.
This error code indicates that parameter x is within an area not allowed for the
system function.
8x26
Parameter contains a time cell number which is too high.
8x27
Parameter contains a counter cell number which is too high.
8x28
8x29
Alignment error on reading parameter.
Alignment error on writing parameter.
The reference to parameter x is an operand whose bit address is not equal to 0.
8x30
8x31
The parameter is located within the write-protected global DB.
The parameter is located within the write-protected instance DB.
8x32
8x34
8x35
The parameter contains a DB number which is too high.
The parameter contains an FC number which is too high.
The parameter contains an FB number which is too high.
8x3A
8x3C
8x3E
The parameter contains a DB number which is not loaded.
The parameter contains an FC number which is not loaded.
The parameter contains an FB number which is not loaded.
8x42
8x43
An access error occurred while the system was attempting to read a parameter from
the I/O area of the inputs.
An access error occurred while the system was attempting to write a parameter to
the I/O area of the outputs.
8x44
8x45
Error on nth (n > 1) read access after an error occurred.
Error on nth (n > 1) write access after an error occurred.
8090
Specified logical base address is invalid: No assignment in SDB1/SDB2x exists, or it
is not a base address.
8092
A type other than BYTE has been specified in an ANY reference.
8093
The area identifier contained in the configuration (SDB1, SDB2x) of the logical
address is not permitted for these SFCs. Permitted:
•
0 = S7-400
•
1 = S7-300
•
2, 7 = DP modules