Alarm, error and system messages
9.2 PROFINET IO
ET 200pro distributed I/O system
228
Operating Instructions, 03/2013, A5E00335544-08
9.2.5.5
Incorrect module combination
Incorrect module combination (packing): USI = W#16#0002
The module in the slot of ET 200pro is invalid in the event of the following configuration
errors:
●
The module combination was started with a module designation containing "*".
●
A module designation with "*" was selected more than once ("*" "*")
9.2.5.6
Diagnostics of faulty configuration states of ET 200pro on PROFINET IO
Faulty configuration states
The following incorrect configuration states of the ET 200pro lead to the failure of the
ET 200pro IO device, or prevent data exchange.
●
Terminating module missing
●
Number of modules exceeds maximum configuration
●
Faulty backplane bus, e.g. defective bus module
Note
If one module is missing (gap) and the ET 200pro is powered on, the startup of the IO device
will fail.
9.2.5.7
Failure of the load voltage from the power module
Load voltage failure
Reaction of the digital electronic modules with outputs to failure of the 2L+ load voltage
supply:
●
The electronic modules do not fail.
●
The outputs are no longer supplied.
●
A diagnostics event is generated if the missing load voltage L+ diagnostics is enabled at
the electronic module 4 DO DC 24V/2.0A High Feature.
Содержание Simatic ET200pro
Страница 8: ...Preface ET 200pro distributed I O system 8 Operating Instructions 03 2013 A5E00335544 08 ...
Страница 16: ...Table of contents ET 200pro distributed I O system 16 Operating Instructions 03 2013 A5E00335544 08 ...
Страница 152: ...Configuring 5 2 PROFINET IO ET 200pro distributed I O system 152 Operating Instructions 03 2013 A5E00335544 08 ...
Страница 188: ...Functions 8 2 PROFINET IO ET 200pro distributed I O system 188 Operating Instructions 03 2013 A5E00335544 08 ...
Страница 545: ...Index ET 200pro distributed I O system Operating Instructions 03 2013 A5E00335544 08 545 ...