Maintenance and service
7.3 Removing and Inserting Electronic Modules
ET 200pro distributed I/O system
160
Operating Instructions, 03/2013, A5E00335544-08
See also
Removing and Inserting Electronic Modules (Page 160)
7.3
Removing and Inserting Electronic Modules
Introduction
The ET 200pro distributed I/O system supports removal and insertion of one electronic
module during operation (one gap).
ET 200pro remains in RUN state when the electronic module is removed.
The ET 200pro station fails if you remove more than one electronic module.
Requirements
●
Hot-swapping of electronic modules (in RUN state) is only supported if the "Operation in
setpoint<> actual configuration" parameter is enabled at the interface module.
●
Only one electronic module may be removed at any given time.
Required tools
●
Cross-tip screwdriver, size 2
●