Connection
4.5 Connecting the interface module to a CM IM DP Direct connection module
ET 200pro distributed I/O system
82
Operating Instructions, 03/2013, A5E00335544-08
Opening and preparing the connection module
1.
Remove the two screws from the bottom of the connection module using a crosstip
screwdriver.
2.
Remove the cover from the connection module.
3.
Install M20 screwed cable glands at the cable inlets using an open-end wrench. The blind
plates will break off automatically when you screw in the glands. Tighten the cable glands
on the connection module (torque = 3 Nm).
4.
Feed the PROFIBUS Hybrid cable through the bottom cable gland in order to achieve a
maximum possible bending radius.
Stripping PROFIBUS Hybrid cables
1.
Strip the PROFIBUS Hybrid over a length of 97 mm.
2.
Remove the white filler material, and the two black fillers of the 4-wire PROFIBUS Hybrid
cable.
3.
Slide the shielding braid back towards the sheath by approx. 15
+/-2
mm.
4.
Carefully strip off the shielding film and the two white fillers from the PROFIBUS DP
cable.
Figure 4-8
Stripping dimensions for PROFIBUS Hybrid cables
Содержание Simatic ET200pro
Страница 8: ...Preface ET 200pro distributed I O system 8 Operating Instructions 03 2013 A5E00335544 08 ...
Страница 16: ...Table of contents ET 200pro distributed I O system 16 Operating Instructions 03 2013 A5E00335544 08 ...
Страница 152: ...Configuring 5 2 PROFINET IO ET 200pro distributed I O system 152 Operating Instructions 03 2013 A5E00335544 08 ...
Страница 188: ...Functions 8 2 PROFINET IO ET 200pro distributed I O system 188 Operating Instructions 03 2013 A5E00335544 08 ...
Страница 545: ...Index ET 200pro distributed I O system Operating Instructions 03 2013 A5E00335544 08 545 ...