Connection modules
11.1 Connection modules for interface modules with PROFIBUS DP
ET 200pro distributed I/O system
250
Operating Instructions, 03/2013, A5E00335544-08
Block diagram
The figure below shows the block diagram of the connection module CM IM DP Direct.
①
Connections for the electronics/encoder supply and load voltage supply
②
Connections for PROFIBUS DP
③
DIP switch for terminating resistor
④
DIP switch for setting the PROFIBUS DP address
Technical specifications
Technical data
Dimensions and weight
Dimensions W x H x D (mm)
90 x 130 x 100
Weight
Approx. 290 g
Currents
Feed current
•
1L+ electronics/encoder supply
Max. 16 A
•
2L+ load voltage supply
Max. 16 A
Note
Feed current
Maximum permissible load on the internal busbars of ET 200pro:
•
At 1L+ 5 A
•
At 2L+ 10 A
See also
IM 154-1 DP interface module (Page 287)
IM 154-2 DP High Feature interface module (Page 294)