Open User Communication
6.6 Setting up communication over FDL
Communication
82
Function Manual, 11/2019, A5E03735815-AH
6.6
Setting up communication over FDL
Requirements
●
Configuration software: STEP 7 Professional V14
●
End point of the connection: CPU S7-1500 firmware version V2.0 or higher with
communication module CM 1542-5 with firmware version V2.0
Setting up a configured FDL connection
Proceed as follows to set up a configured FDL connection in STEP 7:
1.
Create a TSEND_C instruction in the program editor.
2.
Select the TSEND_C instruction and go to "Properties" > "General" > "Connection
parameters" in the Inspector window.
3.
Under End point, select the partner end point. Use one of the two partner end points
below:
–
CPU S7-1500 with CM 1542-5
–
Unspecified
4.
Under Configuration type, select "Use configured connection".
5.
Under Connection type, select "FDL".
6.
Under Interface, select the following interfaces:
–
Local: PROFIBUS interface of CM 1542-5
–
Specified partner: PROFIBUS interface of CM 1542-5
7.
Under Connection data, select the setting <new>.