OPC UA communication
9.3 Using the S7-1500 as an OPC UA server
Communication
Function Manual, 11/2019, A5E03735815-AH
167
Rules
●
Only allow read access to PLC tags and tags of data blocks in STEP 7 if this is necessary
for communication with other systems (controllers, embedded systems or MES).
You should not enable other PLC tags.
●
Only allow write access over OPC UA if write rights are genuinely necessary for specific
PLC tags and tags of data blocks.
●
If you have reset the "Accessible from HMI/OPC UA" option for all elements of a data
block, the data block for an OPC UA client is no longer visible in the address space of the
OPC UA server of the S7-1500 CPU.
●
You can also prevent access to an entire data block centrally (see Managing write and
read rights for a complete DB (Page 167)). This setting "overrules" the settings for the
components in the DB editor.
See also
Coordinating write and read rights for CPU tags (Page 169)
9.3.2.2
Managing write and read rights for a complete DB
Hiding DBs or DB contents for OPC UA clients
You can easily prevent access to a complete data block by an OPC UA client.
With this option, the data of the corresponding DB, including instance DBs of function blocks,
remains hidden for OPC UA clients.
In the default setting, data blocks can be read and written from OPC UA clients. You can
change this default setting in the settings of the TIA Portal: Command "Settings > PLC
programming > General" in "Options" menu. You will find the corresponding option in the
"Default settings for new blocks" area.
Procedure
Proceed as follows to completely hide a data block for OPC UA clients or to protect a data
block from write access from OPC UA clients:
1.
Select the data block to be protected in the project tree.
2.
Select the "Properties" shortcut menu.