OPC UA communication
9.3 Using the S7-1500 as an OPC UA server
Communication
226
Function Manual, 11/2019, A5E03735815-AH
9.3.4.8
Notes on configuration limits when using server interfaces
When you use OPC UA server interfaces, you must comply with limits for the following
objects in line with the S7-1500 CPU performance class:
●
Number of server interfaces
●
Number of OPC UA nodes
●
Load object data volume
●
If you have implemented methods: Number of server methods or server method
instances
Configuration limits for OPC UA server interfaces and methods
The table below sets out the configuration limits for S7-1500 CPUs; these must also be
taken into account when you compile and load a configuration (up-to-date technical
specifications of the CPUs can be found on the Internet
https://support.industry.siemens.com/cs/ww/en/ps/td
)).
A violation of configuration limits results in an error message.
Table 9- 4
Configuration limits for OPC UA server interfaces
Technical specification value
CPU 1510SP (F)
CPU 1511 (C/F/T/TF)
CPU 1512C
CPU 1512SP (F)
CPU 1513 (F)
CPU 1505 (S/SP/SP F/SP T/SP TF)
CPU 1515 (F/T/TF)
CPU 1515 SP PC (F/T/TF)
CPU 1516 (F/T/TF)
CPU 1507S (F)
CPU 1517 (F/T/TF)
CPU 1518 (F)
Use of imported companion specifications (information models)
Maximum number of OPC UA server
interfaces:
•
"Companion specification" type
•
"Reference namespace" type
•
"Server interface" type
10
20
10
10
20
10
10
20
10
•
Maximum number of OPC UA
nodes in user-defined server in-
terfaces
1000
5000
30000
•
Maximum size of loadable OPC
UA server interfaces
1024 KB
5120 KB
15360 KB
Provision of methods
Maximum number of usable server
methods or max. number of server
method instances (instructions
OPC_UA_ServerMethodPre,
OPC_UA_ServerMethodPost)
20
50
100