Communications services
3.2 Communications protocols and port numbers used for Ethernet communication
Communication
24
Function Manual, 11/2019, A5E03735815-AH
Protocol
Port num-
ber
(2) Link layer
(4) Transport layer
Function
Description
Modbus
TCP
Modbus
Transmission
Control Proto-
col
502
(4) TCP
Modbus/TCP protocol
Modbus/TCP is used by
MB_CLIENT/MB_SERVER instructions
in the user program.
OPC UA
Open Platform
Communica-
tions
Unified Archi-
tecture
4840
(4) TCP
Based on the TCP/IP proto-
col
Communication standard ranging from
the enterprise level to the field level.
OUC
1
Open User
Communica-
tion
and
Secure OUC
1 ... 1999
can be used
to limited
extent
2
(4) TCP
(4) UDP
Open User Communication
(TCP/UDP)
Secure Open User Com-
munication (TLS)
OUC instructions provide connection
establishment, connection termination
and data transfer based on the socket
layer.
2000 ...
5000
Recom-
mended
5001 ...
49151
can be used
to limited
extent
2
IGMPv2
Internet Group
Management
Protocol
Not relevant (3) Network layer Internet Group Management
Protocol
Network protocol for the organization of
multicast groups.
Reserved
49152 ...
65535
(4) TCP
(4) UDP
-
Dynamic port area used for active con-
nection end point if the application does
not determine the local port number.
1