Open User Communication
6.5 Setting up Open User Communication via TCP, ISO-on-TCP, UDP and ISO
Communication
Function Manual, 11/2019, A5E03735815-AH
79
7.
Enter a connection ID as needed for the connection partner. No connection ID can be
assigned to an unspecified partner.
Note
You must enter a unique value for the connection ID at a known connection partner. The
uniqueness of the connection ID is not checked by the connection parameter settings and
there is no default value entered for the connection ID when you create a new
connection.
8.
Select the desired connection type in the relevant drop-down list. Default values are set
for the address details depending on the connection type. You can choose between the
following:
–
TCP
–
ISO-on-TCP
–
UDP
–
ISO (only with Configuration mode "Use configured connection")
You can edit the input boxes in the address details. Depending on the selected protocol,
you can edit the ports (for TCP and UDP) or the TSAPs (for ISO-on-TCP and ISO).
9.
Use the "Active connection establishment" check box to set the connection establishment
characteristics for TCP, ISO and ISO-on-TCP. You can decide which communication
partner establishes the connection actively.
Changed values are checked immediately for input errors by the connection configuration
and entered in the data block for the connection description.
Note
Open User Communication between two communication partners can only work when the
program section for the partner end point has been downloaded to the hardware. To achieve
fully functional communication, make sure that you load not only the connection description
of the local CPU on the device but also that of the partner CPU as well.