5.6.5
Grounding the module with a cable
Requirement
• The basics for protective grounding are known.
• The Module is mounted and screwed to the base.
• The cable for grounding has a cross-section >=1.0 mm².
• Required tools:
– TX8 screwdriver for tightening the PE terminal screws
Procedure
1. Remove the washer and terminal screw.
2. Install a cable with a cable lug to the PE terminal of the module. Note the following setup in
doing so:
①
Module
②
Cable lug
③
Washer
④
Clamping screw
⑤
Cable
3. Tighten the PE terminal screw with a torque of 0.51 Nm.
Result
The module is grounded with a cable.
Installation
5.6 Installation
CN 4100 Communication System
34
Equipment Manual, 10/2021, A5E50871363-AA
Содержание SIMATIC CN 4100
Страница 6: ...Table of contents CN 4100 Communication System 6 Equipment Manual 10 2021 A5E50871363 AA ...
Страница 8: ...Security information CN 4100 Communication System 8 Equipment Manual 10 2021 A5E50871363 AA ...
Страница 50: ...Commissioning 7 2 Phases CN 4100 Communication System 50 Equipment Manual 10 2021 A5E50871363 AA ...
Страница 56: ...Operation 8 3 LEDs of the RJ45 port CN 4100 Communication System 56 Equipment Manual 10 2021 A5E50871363 AA ...