When you connect the shielding to ground on only one side (i.e., at the beginning or end of the
line), you limit attenuation to the lower frequencies.
A one-sided shielding connection may be more suitable in the following cases:
• No line for potential equalization can be laid.
• Analog signals (some mA or μA) are transmitted.
• Foil shields (static shields) are used.
Configuration
The following figure shows the configuration of the SIMATIC CN 4100 rack with grounded cable
shields.
①
Grounding screw in grounded state
②
Metal enclosure of the rack (grounded)
③
Ethernet port
5.5
Overview of the installation
The procedure described below shows how to install the SIMATIC CN 4100 communication
system.
Requirement
• The supply voltage is switched off.
• You are familiar with the basics of installing the SIMATIC CN 4100 communication system.
Notes on installation (Page 21)
Installation
5.5 Overview of the installation
CN 4100 Communication System
28
Equipment Manual, 10/2021, A5E50871363-AA