4 Measured Quantities and Recording
4.1 Power Quality Measuring System and Recording System
33
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
4.1.5
Rapid Voltage Change
Rapid voltage change (RVC) is a quick transition of RMS voltage occurring between two steady-state
conditions, and during which the RMS voltage does not exceed the dip/swell threshold.
The threshold of RVC detection is configurable from 1 % up to 6 % of Udin.
The following data and values are determined during the evaluation of the rapid voltage change in SICAM Q100
and listed in the tab
Rapid Voltage Change
(see Chapter 8.4.2.1):
•
RVC event start time
•
RVC event duration
•
∆
V
max
•
∆
V
ss
•
The affected phases (a, b, c, ab, bc, ca, a-b-c).
Figure 4-3
Rapid Voltage Change (RVC)
NOTE
V
rms
(1/2): RMS voltage refreshed each half-cycle according to IEC61000-4-30 Ed. 3.
100/120 V
rms
(1/2) value: 100 values for 50 Hz nominal, or 120 values for 60 Hz nominal.
Содержание SICAM Q100
Страница 8: ...8 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 10: ...10 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 16: ...16 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 88: ...5 Energy Management 5 2 Tariffs 88 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 102: ...6 Getting Started 6 7 Commissioning 102 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 332: ...13 Technical Data 13 3 Dimensions 332 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 370: ...15 Operating Parameters 15 6 Administrative 370 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...