9 Operation at Use of the Display
9.4 Parameterization
295
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
1)
These values are necessary if no Modbus slave device has been configured for the requested Unit ID. If
a Modbus slave device was configured, its values are used.
Table 9-9
Modbus TCP/RTU Gateway Settings
Parameter
Default Setting
Setting Range
Activated
no
no
yes
Unit ID of this device
255
1 to 255
Retry limit
1)
2
0 to 10
Response timeout
1)
50 ms
(1 to 6 000) * 10 ms
= 10 ms to 60 s