8 Operation at Use of a PC
8.3 Configuration of the Device
177
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3.6.5
Memory Management
Default Settings and Setting Ranges
1)
The memory sizes for event list, PQ records, fault records, and mains signalling voltage records can be
changed.
2)
The memory size for continuous recording is calculated automatically and forms the difference to 100 %
of the total memory size. The maximum total memory size of 100 % cannot be exceeded due to
parameterization errors.
3)
If the residual memory capacity falls below 31 %, activation is no longer possible. In this case, the
Action
was not successful
indication appears on the status bar
.
Parameterizing the Memory Allocation
Table 8-17
Memory Management
Parameter
Default Setting
Setting Range
Memory splitting
Event recorder
1.0 %
1 % to 19 %
1)
Measurement recorder
35.0 %
(the recording time depends on
the aggregation interval)
33 % to 51 %
1)
Trend recorder
47.0 %
(residual storage capacity)
Min. 31 %
2) 3)
Fault recorder
3.0 %
(number of records depends on
the fault-record time)
3 % to 21 %
1)
Mains signalling voltage recorder
14 %
(number of records depends on
the record time of the mains sig-
nalling voltage)
14 % to 20 %
1)
NOTE
If the device has been recording data for a longer period, a modification of the memory areas can lead to the
following indication:
„
Memory size should not be changed now. If you active changes, all PQ data will be lost. Please backup data
before activation or cancel changes.
”
This indication is issued only if the stored data and the expected data would exceed the memory capacity of
the SD card.
Содержание SICAM Q100
Страница 8: ...8 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 10: ...10 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 16: ...16 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 88: ...5 Energy Management 5 2 Tariffs 88 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 102: ...6 Getting Started 6 7 Commissioning 102 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 332: ...13 Technical Data 13 3 Dimensions 332 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 370: ...15 Operating Parameters 15 6 Administrative 370 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...