
8 Operation at Use of a PC
8.3 Configuration of the Device
148
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Parameterizing an Indication
✧
Select the desired parameters for an
indication
in the list boxes and option fields (see Figure 8-27,
example terminal G1/G2) as described in Table 8-4.
✧
You can select the following output types in the
Operating mode
list box:
Persistent
: The binary output has the status ON or OFF. If the indication becomes invalid, the binary
output continues to maintain its current status.
Figure 8-28 Persistent
Persistent with fail save
: If the indication becomes invalid, the binary output switches into the OFF
state, that is if
Source inverted
=
no
, or it switches into the ON state if
Source inverted
=
yes
.
Figure 8-29 Persistent with Fail Save
Pulse
without retrigger: This indication is output as pulse. If the indication changes again while the
output pulse is ON, the pulse output time is not restarted. This means that a change of the indication
during the pulse output will be ignored.
Figure 8-30 Pulse without Retrigger
NOTE
If you select
-not assigned-
as the
source
of an
indication
and/or
energy counter
, the corresponding binary
output is inactive.
invalid
Binary output
inverted
Indication
Indication
Output
Binary output
not inverted
invalid
ON
Output
ON
OFF
OFF
ON
OFF
invalid
Binary output
inverted
Indication
Indication
Output
Binary output
not inverted
invalid
ON
Output
ON
OFF
OFF
ON
OFF
Indication
Output
ON
Binary output with
Source inverted = no
OFF
ON
OFF
Output time
Indication
Indication
Indication
Output
Output
Output
Output
Output
Binary output with
Source inverted = yes
ON
OFF
Output time
Содержание SICAM Q100
Страница 8: ...8 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 10: ...10 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 16: ...16 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 88: ...5 Energy Management 5 2 Tariffs 88 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 102: ...6 Getting Started 6 7 Commissioning 102 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 332: ...13 Technical Data 13 3 Dimensions 332 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...
Страница 370: ...15 Operating Parameters 15 6 Administrative 370 SICAM Q100 7KG95xx Device Manual E50417 H1040 C522 A4 Edition 03 2018 ...