Engineering via SICAM TOOLBOX II
196
SICAM RTUs, SICAM AK 3 User Manual
Edition 07.2016, DC2-028-2.03
4.1.9.3 Test Functions
For the examination of the parameterized automation units and their data flows, the following
test functions are available:
•
Data flow test
•
Message simulation
•
Topology test
4.1.9.3.1 Status Of Spontaneous Data Points
With the tool "Data Flow Test" data streams (flow of messages) can be simultaneously logged
and visualized. For a subsequent analysis - also at another location - a recording can take
place with the Interface Recorder.
The function
Simultaneous log
serves for the recording of messages within the internal da-
ta flow of an automation unit. In protocol elements, the data flow from and to other automation
units can also be acquired.
The following data can (with change of the spontaneous data) be simultaneously logged:
•
Change of state of inputs/outputs
•
Communication from and to protocol elements
•
Data traffic from and to the application program
•
Data traffic from and to special functions (for example set counters, set time)
By means of triggering a General Interrogation all spontaneous input signals can be simulta-
neously logged at any arbitrary time.
You find the instruction for this test function in the
SICAM TOOLBOX II Online Help, chapter
"Service Programs“, section "Data Flow Test"
.
You find further information in the manual
SICAM RTUs Common Functions System and
Basic System Elements
, chapter "System Services", section "Data Flow Test".
define TOOLBOX
filters
select test points
select message
display format
play record
select message
display format
logging of the
connected AUs
send message(s)
start record
selection AU
selection AU
total network or
selection AU
data flow
test
message
simulation
topology
test
State of
spontaneous
data points
simulation of
spontaneous
data points
check con-
nection to AUs
Содержание SICAM AK 3
Страница 8: ...Open Source Software 8 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...
Страница 84: ...Installation 84 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...
Страница 119: ...System Components SICAM RTUs SICAM AK 3 User Manual 119 DC2 028 2 03 Edition 07 2016 2 5 3 2 Block Diagram ...
Страница 142: ...System Components 142 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 2 5 5 2 Block Diagram ...
Страница 159: ...System Components SICAM RTUs SICAM AK 3 User Manual 159 DC2 028 2 03 Edition 07 2016 2 8 1 2 Block Diagram ...
Страница 166: ...System Components 166 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...
Страница 180: ...Prepare Engineering 180 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 ...
Страница 260: ...Licensing Agreement 260 SICAM RTUs SICAM AK 3 User Manual Edition 07 2016 DC2 028 2 03 End of document ...