4 Measurands and Recording
4.1 Measuring and Recording System
37
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
You can set the following parameters on the user interface:
•
recording the voltage and/or current
•
activation/deactivation of the fault recorder triggering
•
tolerance unit:
in percent or numerical
•
lower threshold value, referred to U
din
or I
rated
voltage (in percent):
0.00 % to 99.99 %
voltage (numerical):
0.0 V to 1 000 000.0 V
current (in percent):
0.00 % to 99.99 %
current (numerical):
0.0 A to 1 000 000.0 A
•
upper threshold value, referred to U
din
or I
rated
voltage (in percent):
100.0 % to 10 000.0 %
voltage (numerical):
0.0 V to 1 000 000 V
current (in percent):
100.0 % to 10 000.0 %
current (numerical):
0.0 A to 1 000 000 A
•
hysteresis 0.0 % to 50.0 % referred to Udin or Irated