14 Operating Parameters
14.4 Recording and Reporting
252
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
14.4
Recording and Reporting
14.4.1
Event Recorders
14.4.2
Trigger Management
Parameter
Default Setting
Setting Range
Supply Voltage
Swell threshold
110 %
105 % to 140 % in 5-% steps
Dip threshold
90 %
75 % to 95 % in 5-% steps
Interruption threshold
5 %
1 %, 2 %, 3 %, 5 %, 8 % 10 %
Event hysteresis
2 %
1 % to 6 % in 1-% steps
Frequency
Underfrequency threshold
1 %
0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
Overfrequency threshold
1 %
0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
Unbalance
Voltage unbalance threshold
5 %
1 % to 5 % in 1-% steps
Parameter
Default Setting
Setting Range
Voltage trigger limits
Trigger active
no
no
yes
Tolerance unit
Percentage
Percentage
Numerical
Lower threshold
90.00 %
of the of the primary nominal
voltage
0.00 % to 99.99 % of the of the primary
nominal voltage
0.0 V to 1 000 000.0 V
Upper threshold
110.00 %
of the of the primary nominal
voltage
100.0 % to 10 000.0 % of the primary
nominal voltage
0.0 V to 1 000 000.0 V
Содержание SENTRON PAC5100
Страница 8: ...8 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Страница 10: ...10 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Страница 242: ...13 Operational Indications 242 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Страница 264: ...264 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...