14 Operating Parameters
14.4 Recording and Reporting
254
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
14.4.3
Recorder Management
1)
The trend recorder also creates a PQDIF file when 1024 data points have been generated within the re-
cording interval.
Parameter
Default Setting
Setting Range
Measurement Recorder
Average intervals - Frequency
10 s
fixed
Short term flicker
10 min
fixed
Long term flicker
2 h
fixed
Average interval - Voltage /
Unbalance / Harmonics
10 min
30 s, 1 min, 10 min, 15 min, 30 min,
1 h, 2 h
Record additional data (I, P, Q,
S etc.)
no
no
yes
Recorder of average - Min
no
no
yes
Recorder of average - Max
no
no
yes
Harmonics parity
Odd
Even
Odd
All
File generation every:
(corresponds to the setting of
the
Average interval
parame-
ter)
24 h
File generation
every:
At average interval
1 h
30 s
2 h
1 min
2 h
10 min, 15 min,
30 min, 1 h or
2 h
4 h
6 h
12 h
24 h
Recorded file type
PQDIF
PQDIF
CSV
All
Flicker lamp model
230 V
230 V
120 V
Trend Recorder
Tolerance unit
Percentage
Percentage
Numerical
Tolerance number
Percentage: 3 % of declared
input voltage Udin,
Numerical: 0.50 V
1 % to 5 % in 1 % steps
0.20 V to 500.0 V
Maximum recording interval
10 min
10 min, 30 min, 1 h, 2 h, 4 h, 6 h,
12 h, 24 h
1)
Содержание SENTRON PAC5100
Страница 8: ...8 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Страница 10: ...10 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Страница 242: ...13 Operational Indications 242 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Страница 264: ...264 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...