7 Operation at Use of a PC
7.3 Configuration of the Device
122
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Pulse with retrigger
: This indication is output as pulse. The output pulse is retriggered if the
indication is changed during the pulse output. This means that the pulse output is extended.
Figure 7-25 Pulse with Retrigger
✧
If you have selected one of the two
Pulse
types in the
Operating mode
list box, enter an output time x
(in x *10 ms) into the
Output time for pulse operating mode
field.
Behavior when Activating the Set of Parameters after the Set of Parameters was Changed
Persistent
The binary output is set to the new status (ON or OFF) as defined by the current indication.
Pulse
If the binary output is ON in
pulse
mode while activating the parameter set, the binary output is
immediately switched to OFF after the parameter set has been activated. This happens even if the
parameterized
Output time for pulse operating mode
has not yet elapsed.
✧
After the parameterization click
Send
.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
✧
If you do not want to make any additional settings, continue with the
activation
of the device configuration
Activating the Set of Parameters
. If you want to change other settings, enter the
changes and then enable the device configuration as described in section
.
Parameterizing an Energy Counter
(see Figure 7-21, for example terminal G1/2)
✧
Enter the desired values into the fields and select the parameter in the list box as described in Table 7-4.
✧
After the parameterization click
Send
.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
✧
If you do not want to make any additional settings, continue with the
Activation
of the device configuration
Activating the Set of Parameters
. If you want to change other settings, enter the
changes and then enable the device configuration as described in section
.
Indication
Output
Output with retrigger
Binary output with
Source inverted = no
ON
OFF
ON
OFF
Output time
Output time
Indication
Indication
Indication
Indication
Output
Output
Output
Output with
retrigger
Binary output with
Source inverted = yes
Extended output time
ON
OFF
Extended output time
Содержание SENTRON PAC5100
Страница 8: ...8 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Страница 10: ...10 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Страница 242: ...13 Operational Indications 242 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Страница 264: ...264 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...