Connection
7.2 General connection drawings
3KC ATC6500 transfer control device
94
Manual, 05/2019, L1V30538268002A-01
7.2.4
Transfer with contactors
Code
Description
BRK1 / BRK2
Breaker 1 / 2
F1 / F2
Source fuse
Mechanical interlock
Note
Implementation of the power supply
More information on implementing the power supply of the ATC6500 via the inputs 53, 54
and / or the inputs 26, 27 can be found in chapter Connection of the power supply (Page 83).
As shown above, when switching between contactors, the following basic parameters must
be set:
Terminal
Parameter code
Settings
-
P02.01 System configuration
A: 2S-0T
-
P02.22 Management of the tie breaker
(TB)
OFF
-
P08.01 Type of breaker
Contactors
40 (INP1)
P12.1.01 Function of the input INP1
Source 1 breaker closed (feedback 1)
41 (INP2)
P12.2.01 Function of the input INP2
Source 2 breaker closed (feedback 2)
57 (OUT2)
P13.1.01 Function of the output OUT1
Close Source 1 contactor
60 (OUT4)
P13.2.01 Function of the output OUT2
Close Source 2 contactor
Содержание SENTRON ATC6500
Страница 1: ...3KC ATC6500 transfer control device ...
Страница 2: ......
Страница 34: ...Applications 3 3 Voltage measurement 3KC ATC6500 transfer control device 32 Manual 05 2019 L1V30538268002A 01 ...
Страница 35: ...3KC ATC6500 transfer control device Manual 05 2019 L1V30538268002A 01 33 Product description 4 User interface ...
Страница 238: ...Transfer 12 2 Transfer sequence 3KC ATC6500 transfer control device 236 Manual 05 2019 L1V30538268002A 01 ...
Страница 242: ...Technical specifications 3KC ATC6500 transfer control device 240 Manual 05 2019 L1V30538268002A 01 ...
Страница 244: ...Dimension drawings 3KC ATC6500 transfer control device 242 Manual 05 2019 L1V30538268002A 01 Ethernet expansion module ...
Страница 248: ...List of abbreviations 3KC ATC6500 transfer control device 246 Manual 05 2019 L1V30538268002A 01 ...
Страница 256: ......