Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
169
9.4.7
P07 - Breakers
This menu is divided into two sections for Breaker 1 (BRK1) and Breaker 2 (BRK2).
P07
Brk, n = 1…2)
Designation on ATC
display
Description
Unit
De-
fault
Range
P07.n.01
BREAKER
DESCRIPTION
Description of breaker
- This parameter enables the user to define any
name for the breaker.
This name then appears on the Overview display
page.
BRKn (char*6)
P07.n.02
INTERLOCK SOURCE
1/2
Interlocking time Source 1/2
– Delay that elapses between the disconnection of
breaker BRK 1/2 and the opening command for
breaker BRK 2/1.
sec
6
0.1-1800
P07.n.03
FEEDBACK DELAY
Maximum delay for breaker control
(Alarm delay A03 – A04)
- If a breaker is not in the correct position within
this time following an ON or OFF command, alarm
A03 or A04 is triggered.
The parameter only functions if the status inputs
are correspondingly connected and wired.
For more detailed information on the alarms, see
sec
5
1-9000
P07.n.04
OPENING PULSE
TIME
Opening pulse duration
– Minimum duration of an opening command
pulse. For this purpose, the parameter P08.01
must be set to the Pulse mode (Brk. Pul.)
In the application using breakers with motor oper-
ators, a sufficiently long time must be set in order
to enable the complete charging of the springs.
This time is also taken into consideration when
operating in the continuous signal mode.
sec
10
0-600
P07.n.05
CLOSING PULSE
TIME
Duration of closing pulse
– Duration of the closing command pulse.
sec
1
0-600
P07.n.06
CONT. COMMAND IN
OFF
Continuous command in the OFF mode
– This specifies the behavior of the open-
ing/closing command outputs in the continuous
signal mode (P08.01 to Brk. Cont.), if the
ATC6500 is in the OFF mode.
OFF – Opens the command outputs
NOC – Leaves the outputs unchanged
NOC NOC
OFF
P07.n.07
SWITCH AFT. FB
ALARM
Switch on failure to close
- When this parameter is enabled and the breaker
does not close successfully (no feedback on
presence of opening command), not only the
corresponding feedback alarm (A03 or A04) is
triggered, but transfer to the secondary source is
also controlled.
OFF OFF
ON
P07.n.08
MIN COIL PULSE
DUR.
Duration of opening pulse of undervoltage release
– Duration of the disabling pulse of the undervolt-
age release for the opening of the switching de-
vices.
sec
1
0.1-10
Содержание SENTRON ATC6500
Страница 1: ...3KC ATC6500 transfer control device ...
Страница 2: ......
Страница 34: ...Applications 3 3 Voltage measurement 3KC ATC6500 transfer control device 32 Manual 05 2019 L1V30538268002A 01 ...
Страница 35: ...3KC ATC6500 transfer control device Manual 05 2019 L1V30538268002A 01 33 Product description 4 User interface ...
Страница 238: ...Transfer 12 2 Transfer sequence 3KC ATC6500 transfer control device 236 Manual 05 2019 L1V30538268002A 01 ...
Страница 242: ...Technical specifications 3KC ATC6500 transfer control device 240 Manual 05 2019 L1V30538268002A 01 ...
Страница 244: ...Dimension drawings 3KC ATC6500 transfer control device 242 Manual 05 2019 L1V30538268002A 01 Ethernet expansion module ...
Страница 248: ...List of abbreviations 3KC ATC6500 transfer control device 246 Manual 05 2019 L1V30538268002A 01 ...
Страница 256: ......