MODBUS communication
10.4 Data library
3KC ATC6500 transfer control device
192
Manual, 05/2019, L1V30538268002A-01
10.4
Data library
10.4.1
Measured values (use with MODBUS function 03 and 04)
Address Measured value
Unit
Format
02h
Voltage of Source 1 L1-N
V
unsigned long
04h
Voltage of Source 1 L2-N
V
unsigned long
06h
Voltage of Source 1 L3-N
V
unsigned long
08h
Voltage of Source 1 L1-L2
V
unsigned long
0Ah
Voltage of Source 1 L2-L3
V
unsigned long
0Ch
Voltage of Source 1 L3-L1
V
unsigned long
0Eh
Voltage of Source 2 L1-N
V
unsigned long
10h
Voltage of Source 2 L2-N
V
unsigned long
12h
Voltage of Source 2 L3-N
V
unsigned long
14h
Voltage of Source 2 L1-L2
V
unsigned long
16h
Voltage of Source 2 L2-L3
V
unsigned long
18h
Voltage of Source 2 L3-L1
V
unsigned long
1Ah
Frequency Source 1
Hz/10
unsigned long
1Ch
Frequency Source 2
Hz/10
unsigned long
1Eh
Battery voltage (DC source)
VDC/10 unsigned long
20h
Total operation time
s
unsigned long
22h
Time Source 1 OK
s
unsigned long
24h
Time Source 2 OK
s
unsigned long
26h
Time Source 1 not OK
s
unsigned long
28h
Time Source 2 not OK
s
unsigned long
2Ah
Time that Source 1 breakers (BRK1) are closed
s
unsigned long
2Ch
Time that Source 2 breakers (BRK2) are closed
s
unsigned long
2Eh
Total time breakers open
s
unsigned long
30h
Not used
--
unsigned long
32h
Number of operations for Source 1 breaker (BRK1) in automatic mode
no.
unsigned long
34h
Number of operations for Source 2 breaker (BRK1) in automatic mode
no.
unsigned long
36h
Number of operations for Source 1 breaker (BRK1) in manual mode
no.
unsigned long
38h
Number of operations for Source 2 breaker (BRK1) in manual mode
no.
unsigned long
3Ah
Number of alarms when changing over to Breaker 1 (BRK1)
no.
unsigned long
3Ch
Number of alarms when changing over to Breaker 2 (BRK1)
no.
unsigned long
3Eh
Not used
--
unsigned long
50h
Minimum battery voltage
V DC
unsigned long
52h
Maximum battery voltage
V DC
unsigned long
54h
Maintenance hours Source 1
no.
unsigned long
56h
Maintenance hours Source 2
no.
signed long
58h
Maintenance operations Source 1
no.
signed long
Содержание SENTRON ATC6500
Страница 1: ...3KC ATC6500 transfer control device ...
Страница 2: ......
Страница 34: ...Applications 3 3 Voltage measurement 3KC ATC6500 transfer control device 32 Manual 05 2019 L1V30538268002A 01 ...
Страница 35: ...3KC ATC6500 transfer control device Manual 05 2019 L1V30538268002A 01 33 Product description 4 User interface ...
Страница 238: ...Transfer 12 2 Transfer sequence 3KC ATC6500 transfer control device 236 Manual 05 2019 L1V30538268002A 01 ...
Страница 242: ...Technical specifications 3KC ATC6500 transfer control device 240 Manual 05 2019 L1V30538268002A 01 ...
Страница 244: ...Dimension drawings 3KC ATC6500 transfer control device 242 Manual 05 2019 L1V30538268002A 01 Ethernet expansion module ...
Страница 248: ...List of abbreviations 3KC ATC6500 transfer control device 246 Manual 05 2019 L1V30538268002A 01 ...
Страница 256: ......