Parameterization
9.4 Parameters
3KC ATC6500 transfer control device
164
Manual, 05/2019, L1V30538268002A-01
P02
Designation on ATC
display
Description
Unit
Default Range
P02.32 POST-TRANSFER
TIME 1
Post-transfer time Load 1
– After a transfer between the sources, this parame-
ter defines when the Post-transfer Load 1 output is
enabled. For more information, see chapter Table of
functions of the digital outputs (Page 150).
s
OFF
OFF /
1…1000
P02.33 PRE-TRANSFER
TIME 2
Pre-transfer time Load 2
– Delay between enabling the output Pre-transfer
Load 2 and the actual shutting down of the load. An
output must be parameterized with the function Pre-
transfer time Load 2 for this purpose. For more
information, see chapter Table of functions of the
s
OFF
OFF /
1…1000
P02.34 POST-TRANSFER
TIME 2
Post-transfer time Load 2
– After a transfer between the sources, this parame-
ter defines when the Post-transfer Load 2 output is
enabled. For more information, see chapter Table of
functions of the digital outputs (Page 150).
s
OFF
OFF /
1…1000
P02.37 CONT. COM. TB IN
OFF
Continuous command of tie breaker TB in OFF
mode
– This specifies the behavior of the opening/closing
command outputs in the continuous signal mode, if
the ATC6500 is in the OFF mode. Used in applica-
tions with contactors.
OFF – Opens the command outputs
NOC – Leaves the outputs unchanged
NOC
OFF
NOC
P02.39 TB. EN. CONDITION Enabling of tie breaker TB
– This parameter enables you to specify how and
whether the tie breaker is to be controlled.
OFF = The tie breaker is controlled normally
Other selection = The tie breaker can only be con-
trolled if the selected condition is met.
Example: On selecting INPx, the tie breaker can
only be controlled if the corresponding input is ac-
tive.
OFF
OFF
INPx
OUTx
LIMx
REMx
Ax
UAx
TIMx
P02.40 CHANNEL NO.
Function index
– Index that is possibly assigned to the function
programmed in the previous parameter. Example:
The tie breaker TB should only be controllable if the
input 4 has been enabled: P02.39 = INPx P0240 =
4
OFF
OFF / 1-99
P02.43 INTERLOCK TB
Interlock time of tie breaker TB
– Delay that elapses between disconnection of the
tie breaker and the opening command for the
source breakers.
sec
6
0.1 - 1800
Содержание SENTRON ATC6500
Страница 1: ...3KC ATC6500 transfer control device ...
Страница 2: ......
Страница 34: ...Applications 3 3 Voltage measurement 3KC ATC6500 transfer control device 32 Manual 05 2019 L1V30538268002A 01 ...
Страница 35: ...3KC ATC6500 transfer control device Manual 05 2019 L1V30538268002A 01 33 Product description 4 User interface ...
Страница 238: ...Transfer 12 2 Transfer sequence 3KC ATC6500 transfer control device 236 Manual 05 2019 L1V30538268002A 01 ...
Страница 242: ...Technical specifications 3KC ATC6500 transfer control device 240 Manual 05 2019 L1V30538268002A 01 ...
Страница 244: ...Dimension drawings 3KC ATC6500 transfer control device 242 Manual 05 2019 L1V30538268002A 01 Ethernet expansion module ...
Страница 248: ...List of abbreviations 3KC ATC6500 transfer control device 246 Manual 05 2019 L1V30538268002A 01 ...
Страница 256: ......