Description of blocks
3.2 Driver module DRV_3WL
Library SENTRON 3WL / 3VL for SIMATIC PCS 7
Function Manual, 11/2008, A5E02316914A-01
57
I/O (parameter)
Comment
Data type
Default
Type OCM
EARTH_FLT_CUR_NA
DR 129: Determination of earth fault
current not available
BOOL
FALSE
O
x
R_CUR_GRD_FLT
DR 129: Rated current ground fault
transformer
REAL
0.0
O
x
R_CUR_GRD_FLT_QC
Quality code of R_CUR_GRD_FL
BYTE
0
O
R_CUR_GRD_FLT_OFF
DR 129: Rated current ground fault
transformer OFF
BOOL
FALSE
O
x
R_CUR_GRD_FLT_NA
DR 129: Rated current ground fault
transformer not available
BOOL
FALSE
O
x
MLFB
DR 129: Catalog number CB as upgraded
or changed by cust. or service (text)
STRING[18]
O
x
MLFB_QC
Quality code of MLFB
BYTE
0
O
MLFB_OFF
DR 129: Catalog number CB as upgraded
or changed by cust. or service (text) OFF
BOOL
FALSE
O
x
MLFB_NA
DR 129: Catalog number CB as upgraded
or changed by cust. or service (text) not
available
BOOL
FALSE
O
x
RP_NORM_O
DR 130: Real power in normal direction
REAL
0.0
O
RP_NORM_O_QC
Quality code of RP_NORM_O
BYTE
0
O
RP_REV_O
DR 130: Real power in reverse direction
REAL
0.0
O
RP_REV_O_QC
Quality code of RP_REV_O
BYTE
0
O
PF_CAP_O
DR 130: Power factor capacitive
REAL
0.0
O
PF_CAP_O_QC
Quality code of PF_CAP_O
BYTE
0
O
PF_IND_O
DR 130: Power factor inductive
REAL
0.0
O
PF_IND_O_QC
Quality code of PF_IND_O
BYTE
0
O
T_RP_NORM_O
DR 130: Delay time for real power in
normal direction
REAL
0.0
O
T_RP_NORM_O_QC
Quality code of T_RP_NORM_O
BYTE
0
O
T_RP_REV_O
DR 130: Delay time for real power in
reverse direction
REAL
0.0
O
T_RP_REV_O_QC
Quality code of T_RP_REV_O
BYTE
0
O
T_PF_CAP_O
DR 130: Delay time for power factor
capacitive
REAL
0.0
O
T_PF_CAP_O_QC
Quality code of T_PF_CAP_O
BYTE
0
O
T_PF_IND_O
DR 130: Delay time for power factor
inductive
REAL
0.0
O
T_PF_IND_O_QC
Quality code of T_PF_IND_O
BYTE
0
O
OVER_FRQ_O
DR 130: Over frequency
REAL
0.0
O
OVER_FRQ_O_QC
Quality code of OVER_FRQ_O
BYTE
0
O
T_OVER_FRQ_O
DR 130: Delay time for over frequency
REAL
0.0
O
T_OVER_FRQ_O_QC
Quality code of T_OVER_FRQ_O
BYTE
0
O
UNDER_FRQ_O
DR 130: Under frequency
REAL
0.0
O
UNDER_FRQ_O_QC
Quality code of UNDER_FRQ_O
BYTE
0
O
T_UNDER_FRQ_O
DR 130: Delay time for under frequency
REAL
0.0
O
T_UNDER_FRQ_O_QC
Quality code of T_UNDER_FRQ_O
BYTE
0
O