Description of blocks
3.2 Driver module DRV_3WL
Library SENTRON 3WL / 3VL for SIMATIC PCS 7
Function Manual, 11/2008, A5E02316914A-01
27
Auxiliary values
EV_ID
Auxiliary value
Block parameters
1
AUX_PR01
2
AUX_PR02
3
AUX_PR03
4
AUX_PR04
5
AUX_PR05
6
AUX_PR06
7
AUX_PR07
8
AUX_PR08
9
AUX_PR09
MSG_EVID1
-
MSG_EVID2
10
AUX_PR10
3.2.5
Assignment of the cyclic process image
Only basic type 3 is supported in the default setting.
Name
Inputs
Outputs
0 / 1
Control bytes
2
0 / 1
Binary status information
2
2 / 3
Current in phase 1
2
4 / 5
Current in phase 2
2
6 / 7
Current in phase 3
2
8 / 9
Max. current in phase under highest load
2
10 / 11 Current in neutral conductor
2
12 / 13 Phase-to-phase voltage L12
2
14 / 15 Phase-to-phase voltage L23
2
16 / 17 Phase-to-phase voltage L31
2
18 / 19 Neutral-point star voltage L1N
2
20 / 21 Neutral-point star voltage L2N
2
22 / 23 Neutral-point star voltage L3N
2
24 / 25 Mean value of power factors of 3 phases
2
26 / 27 Total active energy of 3 phases
2
28 / 29 Total apparent power of 3 phases
2
30
EB of current phase 1
1
31
EB of current phase 2
1
32
EB of current phase 3
1
33
EB of max. current in phase under highest load
1
34
EB of current in neutral conductor
1
35
EB of phase-to-phase voltage L12
1