Description of blocks
3.3 Driver module DRV_3VL
Library SENTRON 3WL / 3VL for SIMATIC PCS 7
Function Manual, 11/2008, A5E02316914A-01
105
I/O (parameter)
Comment
Data type
Default
Type OCM
R_MAINT
Reset all resettable maintenance information
and counters
BOOL
FALSE
IO
x
MAINT
1 = Maintenance mode
BOOL
FALSE
IO
x
QERR
1 = Error
BOOL
FALSE
O
x
QMON_ERR
1 = Monitoring error
BOOL
FALSE
O
x
QBAD
1 = Bad process value
BOOL
FALSE
O
x
QMSG_SUP
1 = Message suppression active
BOOL
FALSE
O
x
QMSG_ERR
1 = Message error
BOOL
FALSE
O
QDIAG_REQ
1 = Read diagnostic information
BOOL
FALSE
O
QMANOP
1 = Operator enabled for MANUAL
BOOL
FALSE
O
x
QAUTOP
1 = Operator enabled for AUTO
BOOL
FALSE
O
x
QOFF_OP
1 = Operator enabled for "OFF"
BOOL
FALSE
O
x
QON_OP
1 = Operator enabled for "ON"
BOOL
FALSE
O
x
QRES_OP
1 = Operator enabled for "RESET"
BOOL
FALSE
O
x
QDR_OP
1 = Operator enabled for data record actions BOOL
FALSE
O
x
QOP_ERR
1 = Operator error
BOOL
FALSE
O
QMAN_AUT
1 = AUTO, 0 = MANUAL mode
BOOL
FALSE
O
x
MSG_STAT1
Message block 1: STATUS Output
WORD
0
O
MSG_STAT2
Message block 2: STATUS Output
WORD
0
O
MSG_ACK1
Message block 1: ACK_STATE Output
WORD
0
O
MSG_ACK2
Message block 2: ACK_STATE Output
WORD
0
O
QERR_WR
1 = An error occurred during writing DRs
BOOL
FALSE
O
QERR_RD
1 = An error occurred during reading DRs
BOOL
FALSE
O
QWR_STAT
Status of DR writing
WORD
0
O
QRD_STAT
Status of DR reading
WORD
0
O
STATUS
Binary status information
WORD
0
O
STATUS_QC
Quality code of STATUS
BYTE
16#80
O
CUR_L1
Current in phase 1
REAL
0.0
O
x
CUR_L1_QC
Quality code of CUR_L1
BYTE
16#80
O
CUR_L2
Current in phase 2
REAL
0.0
O
x
CUR_L2_QC
Quality code of CUR_L2
BYTE
16#80
O
CUR_L3
Current in phase 3
REAL
0.0
O
x
CUR_L3_QC
Quality code of CUR_L3
BYTE
16#80
O
CUR_MAX
Current max. L1, L2, L3
REAL
0.0
O
x
CUR_MAX_QC
Quality code of CUR_MAX
BYTE
16#80
O
CUR_N
Current in phase N (trip unit)
REAL
0.0
O
x
CUR_N_QC
Quality code of CUR_N
BYTE
16#80
O
ST_CB
Status of circuit breaker
BYTE
0
O
x
QNOT_RDY
1 = Circuit breaker not ready
BOOL
FALSE
O
QOFF
1 = Main contacts disconnected
BOOL
FALSE
O
QON
1 = Main contacts closed
BOOL
FALSE
O
QTRIP
1 = Circuit breaker has tripped
BOOL
FALSE
O