Description of blocks
3.2 Driver module DRV_3WL
Library SENTRON 3WL / 3VL for SIMATIC PCS 7
36
Function Manual, 11/2008, A5E02316914A-01
I/O (parameter)
Comment
Data type
Default
Type OCM
RD_DR92
Read data record 92 (diagnostics)
BOOL
FALSE
IO
x
RD_DR128
Read data record 128 (metering and ext.
protective function)
BOOL
FALSE
IO
x
RD_DR129
Read data record 129 (protective function) BOOL
FALSE
IO
x
RD_DR130
Read data record 130 (setpoints)
BOOL
FALSE
IO
x
WR_DR130
Write data record 130 (setpoints)
BOOL
FALSE
IO
x
AUT_ON_OP
Operator input: Mode 1 = AUTO,
0 = MANUAL
BOOL
FALSE
IO
x
AUX_PR01
Auxiliary value 01
ANY
IO
AUX_PR02
Auxiliary value 02
ANY
IO
AUX_PR03
Auxiliary value 03
ANY
IO
AUX_PR04
Auxiliary value 04
ANY
IO
AUX_PR05
Auxiliary value 05
ANY
IO
AUX_PR06
Auxiliary value 06
ANY
IO
AUX_PR07
Auxiliary value 07
ANY
IO
AUX_PR08
Auxiliary value 08
ANY
IO
AUX_PR09
Auxiliary value 09
ANY
IO
AUX_PR10
Auxiliary value 10
ANY
IO
MAN_OFF
Operator input: Switch off (open the main
contacts)
BOOL
FALSE
IO
x
MAN_ON
Operator input: Switch on (close the main
contacts)
BOOL
FALSE
IO
x
RESET
Operator input trip reset
BOOL
FALSE
IO
x
RES_MONERR
Operator input reset monitoring error
BOOL
FALSE
IO
x
ACK_TRIP
A current trip is acknowledged and reset
BOOL
FALSE
IO
x
DEL_TRIP
Delete trip and event log
BOOL
FALSE
IO
x
R_VAL_MEM
Reset all min./max. value memories
(except temperatures)
BOOL
FALSE
IO
x
R_TEMP
Reset min./max. temperatures
BOOL
FALSE
IO
x
R_MAINT
Reset all resettable maintenance
information and counters
BOOL
FALSE
IO
x
MAINT
1 = Maintenance mode
BOOL
FALSE
IO
x
QERR
1 = Error
BOOL
FALSE
O
x
QMON_ERR
1 = Monitoring error
BOOL
FALSE
O
x
QBAD
1 = Bad process value
BOOL
FALSE
O
x
QMSG_SUP
1 = Message suppression active
BOOL
FALSE
O
x
QMSG_ERR
1 = Message error
BOOL
FALSE
O
QMANOP
1 = Operator enabled for MANUAL
BOOL
FALSE
O
x
QDIAG_REQ
1 = Read diagnostic information
BOOL
FALSE
O
QAUTOP
1 = Operator enabled for AUTO
BOOL
FALSE
O
x
QOFF_OP
1 = Operator enabled for "OFF"
BOOL
FALSE
O
x
QON_OP
1 = Operator enabled for "ON"
BOOL
FALSE
O
x
QRES_OP
1 = Operator enabled for "RESET"
BOOL
FALSE
O
x