Description of blocks 

 

3.3 Driver module DRV_3VL 

 

Library SENTRON 3WL / 3VL for SIMATIC PCS 7 

116

 

Function Manual, 11/2008, A5E02316914A-01 

 

Element (parameters) 

Meaning 

Display when 3VL is connected 

following Y-link 

CUR_L1 

Current in phase L1 

Yes 

CUR_L2 

Current in phase L2 

Yes 

CUR_L3 

Current in phase L3 

Yes 

CUR_N 

Current in neutral conductor 

Yes 

CUR_DEM_L1 

Demand for current L1 

No 

CUR_DEM_L2 

Demand for current L2 

No 

CUR_DEM_L3 

Demand for current L3 

No 

CUR_DEM3 

Demand for 3-phase current 

No 

CUR_UNBAL 

Phase unbalance current (as %) 

No 

CUR_DEM3PH 

Mean current value over the three phases 

No 

CUR_EARTH_F 

Current which flows to earth 

No 

FRQ 

Frequency 

No 

Diagnosis  

 

(1) 

WRN_NO1 

(2) 

WRN_NO2 

(3) 

WRN_NO3 

(4) 

WRN_NO4 

(5) 

WRN_NO5 

(6) 

WRN_NO6 

(7) 

WRN_NO7 

(8) 

WRN_NO8 

Figure 3-31  Faceplate for diagnosis view 

Содержание SENTRON 3WL

Страница 1: ...SENTRON 3WL 3VL Library for SIMATIC PCS 7 V1 0 Function Manual 11 2008 SIMATIC ...

Страница 2: ......

Страница 3: ...1 Information about the library 2 Description of blocks 3 Configuration Manual 4 Technical specifications 5 Technical support 6 Library SENTRON 3WL 3VL for SIMATIC PCS 7 Function Manual 11 2008 A5E02316914A 01 V1 0 ...

Страница 4: ...erformed by qualified personnel Within the context of the safety notes in this documentation qualified persons are defined as persons who are authorized to commission ground and label devices systems and circuits in accordance with established safety practices and standards Proper use of Siemens products Note the following WARNING Siemens products may only be used for the applications described in...

Страница 5: ... 19 3 1 7 Module fault 19 3 1 8 Read diagnostics data of 3WL 3VL 19 3 1 9 Start up characteristics 20 3 1 10 Block parameters 20 3 2 Driver module DRV_3WL 22 3 2 1 Calling OBs 22 3 2 2 Called blocks 23 3 2 3 Function 23 3 2 4 Message behavior 26 3 2 5 Assignment of the cyclic process image 27 3 2 6 Addressing and module driver 28 3 2 7 Processing the diagnostics data of the 3WL device 28 3 2 8 Sta...

Страница 6: ... 3WL 8 Figure 1 3 Selection of basic type for 3VL 9 Figure 1 4 Properties of the 3WL 3VL device directly connected to the DP master system 10 Figure 1 5 Properties of the 3WL 3VL device following a Y link 11 Figure 2 1 Section of the overview display 13 Figure 2 2 Trend setting on the icon 14 Figure 2 3 Icons in Graphics Designer 15 Figure 3 1 Symbol with 1 measurement 61 Figure 3 2 Faceplate for ...

Страница 7: ...ctive power tab 94 Figure 3 27 Faceplate for message suppression view 95 Figure 3 28 Symbol with 1 measurement 111 Figure 3 29 Faceplate for standard view 113 Figure 3 30 Faceplate for measurements view 115 Figure 3 31 Faceplate for diagnosis view 116 Figure 3 32 Faceplate for maintenance view maintenance 1 tab 118 Figure 3 33 Faceplate for maintenance view operation tab 119 Figure 3 34 Faceplate ...

Страница 8: ...L 3VL for SIMATIC PCS 7 6 Function Manual 11 2008 A5E02316914A 01 Figure 4 11 Creating block icons out of plant hierarchy 136 Figure 4 12 Create block icons when compiling OS 136 Figure 4 13 Link picture component with measuring point 137 ...

Страница 9: ...of a 3VL circuit breaker User objects and operating blocks for operating and observing measured data on the OS Online help in German and English Manual in German and English The block library can be used in in the PCS 7 versions V6 1 SP1 V7 0 and V7 0 SP1 1 2 Further documentation You can find further details in the following manuals Manual for SENTRON WL and SENTRON VL circuit breakers with commu...

Страница 10: ... cases ensure that the circuit breaker s I O data is within the control s process image This is absolutely essential to the driver generator s functionality 1 4 1 Incorporating via GSD file If the 3WL 3VL device is incorporated via GSD SIEM80C0 gsd it is entered in the hardware configuration catalog under PROFIBUS DP Other field devices Switchgear Figure 1 1 Catalog path for incorporating via GSD ...

Страница 11: ...r 3WL This basic type must be set to ensure operation The following I O configuration applies for 3VL Outputs 2 bytes of digital control data Inputs 14 bytes of binary status 2 bytes and measurements with property bytes 12 bytes Figure 1 3 Selection of basic type for 3VL This configuration corresponds to basic type 1 for 3VL This basic type must be set to ensure operation ...

Страница 12: ...C PCS 7 10 Function Manual 11 2008 A5E02316914A 01 Configuration in HW config In the HW config 3WL 3VL is installed with the corresponding GSD file see above and with basic type 3 and or 1 Figure 1 4 Properties of the 3WL 3VL device directly connected to the DP master system ...

Страница 13: ...r be read from the device For details of the effect that this has on the response of the blocks refer to Section 3 Description of the blocks Page 17 Figure 1 5 Properties of the 3WL 3VL device following a Y link The start addresses of inputs and outputs must be located in the partial process image that is assigned to the watchdog interrupt OB in which the driver block is called The LADDR parameter...

Страница 14: ...Introduction 1 4 Hardware configuration Library SENTRON 3WL 3VL for SIMATIC PCS 7 12 Function Manual 11 2008 A5E02316914A 01 ...

Страница 15: ...rd views Trend Batch and Alarm provided by the Faceplate Designer If other user objects and functions are required they can be added The faceplates described are provided as functional and tested examples and can be adapted by the user Two icons and a group loop display with all the necessary displays are provided for the driver block The relevant group display is called using the icons Overview T...

Страница 16: ...th and StandardTrend properties must be parameterized on the icon to incorporate a trend in a faceplate 2 Online values with 5 min time axis StandardTrend 2 Archive values with time axis of the value entered in min AVGCUR Structural element name starting with a full stop Separators CO_GREEN Color for trend ReturnPath Separators between two online values Figure 2 2 Trend setting on the icon ...

Страница 17: ...bute The value of this attribute describes the variant For example if you look at a variant of the block icon for a valve you will find the value Valve 2 You use the part of the value displayed after the to control which variant of the block icon is produced You therefore have to enter this part in the object properties for the block instance If you do not enter any parameters in the object proper...

Страница 18: ...Information about the library 2 2 General information about OS typicals Library SENTRON 3WL 3VL for SIMATIC PCS 7 16 Function Manual 11 2008 A5E02316914A 01 ...

Страница 19: ...1 Diagnostics block DIA_WLVL FB1742 The DRV_3WL and DRV_3VL driver blocks have a shared diagnostics block DIA_WLVL Description of block Calling OBs Page 18 Called blocks Page 18 Function Page 18 Message behavior Page 18 Error behavior Page 19 I O access error Page 19 Module fault Page 19 Read diagnostics data of 3WL 3VL Page 19 Start up characteristics Page 20 Block parameters Page 20 See also Dri...

Страница 20: ...he block evaluates the acyclic events that are relevant for 3WL 3VL start up DP station failure module fault generates quality code and diagnostic information for the MOD_PAX0 block and provides the driver block with status information via parameter output OMODE In the case of operation following a Y link DPV1 diagnostic information cannot be supplied to the driver block The block evaluates start ...

Страница 21: ...when ACC_ID TRUE the module addressed with LADDR is checked SZL ID xC91 is read for this purpose If the module addressed with LADDR does not exist the output QMODF is set and the identifier for higher ranking error is entered for the OMODE output OMODE 16 40xxxxxx 3 1 8 Read diagnostics data of 3WL 3VL If the 3WL 3VL outputs a diagnostics alarm system function RDSYSST SFC51 will activate reading o...

Страница 22: ...t Data type Default Type OCM EN_DIAG 1 Enable read diagnostic data BOOL FALSE I MODE Parameter OMODE of DRV_WLVL WORD 0 I LADDR Logical address of module INT 0 I DADDR Diagnostic address of module INT 0 I DPA_LINK Device connection 0 DP MASTER 1 DP PA LINK BOOL FALSE I SUBN_TYP 1 External DP interface BOOL FALSE I SUBN1_ID ID of Primary Subnet BYTE 16 FF I SUBN2_ID ID of Redundant Subnet BYTE 16 F...

Страница 23: ...IAG Diagnostic information for maintenance DWORD 0 O QDIAG_INF Diagnostic information WORD 0 O Structure of OMODE Byte Value Meaning Byte 3 16 80 Valid data 16 40 Invalid data Higher level fault Byte 2 16 01 Cold restart OB100 Byte 1 0 16 0000 Irrelevant Structure of QDIAG_INF VALUE Meaning 0 Everything ok 1 Perform visual inspection on main contacts 2 Immediate maintenance of main contacts ...

Страница 24: ...ignment of the cyclic process image Page 27 Addressing and module driver Page 28 Processing the diagnostics data of the 3WL device Page 28 Start up characteristics Page 29 Block parameters Page 29 Description of symbols and faceplates Page 60 See also Diagnostics block DIA_WLVL Page 17 Driver module DRV_3VL Page 95 3 2 1 Calling OBs The OB watchdog interrupt in which the block is installed e g OB3...

Страница 25: ...he faceplate and the circuit breaker is controlled by input parameters which can be connected in the CFC AUTO_ON AUTO_OFF and therefore by the AS program The user can define the mode in which the block is to run in the faceplate or in a block parameter AUT_L The setting at the LIOP_SEL input determines which of the parameters is currently active NOTICE If an error occurs monitoring error Local tur...

Страница 26: ...it breaker is not ready for an On command RDY_ON 0 It must not be switched off when there is a monitoring error QMON_ERR 1 the block is in maintenance mode MAINT 1 write protection applies QWR_PROT 1 the circuit breaker is already off QOFF 1 the circuit breaker has tripped QTRIP 1 the circuit breaker has been switched off locally QLOC_OFF 1 Resetting Tripped and Local turn off states If the block ...

Страница 27: ...ord is read in a defined cycle The interval at which the data record can be read can be set in seconds using the input parameter CYCLE_T The default setting is 60 seconds A cycle of 0 seconds or less means that this data record is not read Time synchronization Data record 68 writes the current time in cycles in order to transfer the current time to the circuit breaker This cycle can be set in seco...

Страница 28: ...age text Message class 1 Overload tripping L AH 2 Instantaneous short circuit I AH 3 Short time delay short circuit S AH 4 Ground fault G AH 5 Trip as a result of extended protection function AH 6 Overload in neutral conductor AH 7 Overload warning present WH MSG_EVID1 8 An activated setpoint value has been exceeded WH 1 An alarm signal is currently present WH 2 Error time synchronization WH 3 Loc...

Страница 29: ...n phase 1 2 4 5 Current in phase 2 2 6 7 Current in phase 3 2 8 9 Max current in phase under highest load 2 10 11 Current in neutral conductor 2 12 13 Phase to phase voltage L12 2 14 15 Phase to phase voltage L23 2 16 17 Phase to phase voltage L31 2 18 19 Neutral point star voltage L1N 2 20 21 Neutral point star voltage L2N 2 22 23 Neutral point star voltage L3N 2 24 25 Mean value of power factors...

Страница 30: ...t QDIAG_INF of diagnostics block DIA_WLVL In the case of operation following a Y Link DPV1 the module driver connects block inputs MODE RACKF and DIAG_INF to outputs OMODE QRACKF and QDIAG_INF of diagnostics block DIA_WLVL In the case of operation following a Y Link DPV0 the module driver connects block inputs MODE and RACKF to outputs OMODE00 and QRACKF of block PADP_L00 The block input BASADR is...

Страница 31: ... of DRs s REAL 60 0 I TIME_SYNC_T Cycle time of time synchronization min REAL 10 0 I DIAREQ_T Cycle time of reading diagnostic information min BOOL FALSE O DR94_K 1 kWh inputs for real and reactive energy of DR 94 are used BOOL FALSE I x MONITOR 1 Monitoring activated BOOL TRUE I TIME_MON Monitoring time s REAL 10 0 I DIAG_INF Diagnostic info for driver WORD 0 I ALT_SYM 1 Alternative symbols BOOL ...

Страница 32: ...uality code of PF_IND_I BYTE 0 I PF_IND_I_OFF DR 130 Power factor inductive OFF BOOL FALSE I x PF_IND_I_NA DR 130 Power factor inductive not available BOOL FALSE I x T_RP_NORM_I DR 130 Delay time for real power in normal direction REAL 0 0 I x T_RP_NORM_I_QC Quality code of T_RP_NORM_I BYTE 0 I T_RP_NORM_I_OFF DR 130 Delay time for real power in normal direction OFF BOOL FALSE I x T_RP_NORM_I_NA D...

Страница 33: ...0 Delay time for under frequency REAL 0 0 I x T_UNDER_FRQ_I_QC Quality code of T_UNDER_FRQ_I BYTE 0 I T_UNDER_FRQ_I_OFF DR 130 Delay time for under frequency OFF BOOL FALSE I x T_UNDER_FRQ_I_NA DR 130 Delay time for under frequency not available BOOL FALSE I x CUR_THD_I DR 130 THD current REAL 0 0 I x CUR_THD_I_QC Quality code of CUR_THD_I BYTE 0 I CUR_THD_I_OFF DR 130 THD current OFF BOOL FALSE I...

Страница 34: ...and real power REAL 0 0 I x RP_DEM_I_QC Quality code of PR_DEM_I BYTE 0 I RP_DEM_I_OFF DR 130 Demand real power OFF BOOL FALSE I x RP_DEM_I_NA DR 130 Demand real power not available BOOL FALSE I x AP_DEM_I DR 130 Demand apparent power REAL 0 0 I x AP_DEM_I_QC Quality code of AP_DEM_I BYTE 0 I AP_DEM_I_OFF DR 130 Demand apparent power OFF BOOL FALSE I x AP_DEM_I_NA DR 130 Demand apparent power not ...

Страница 35: ...I x T_RAP_NORM_I_NA DR 130 Delay time for reactive power in normal direction not available BOOL FALSE I x RAP_REV_I DR 130 Reactive power in reverse direction REAL 0 0 I x RAP_REV_I_QC Quality code of RAP_REV_I BYTE 0 I RAP_REV_I_OFF DR 130 Reactive power in reverse direction OFF BOOL FALSE I x RAP_REV_I_NA DR 130 Reactive power in reverse direction not available BOOL FALSE I x AP_I DR 130 Apparen...

Страница 36: ...BOOL FALSE I x T_CUR_OVER_I DR 130 Delay time for over current REAL 0 0 I x T_CUR_OVER_I_QC Quality code of T_CUR_OVER_I BYTE 0 I T_CUR_OVER_I_OFF DR 130 Delay time for over current OFF BOOL FALSE I x T_CUR_OVER_I_NA DR 130 Delay time for over current not available BOOL FALSE I x T_CUR_GRD_I DR 130 Delay time for over current ground REAL 0 0 I x T_CUR_GRD_I_QC Quality code of T_CUR_GRD_I BYTE 0 I ...

Страница 37: ..._UNDER_VOLT_I_NA DR 130 Delay time for under voltage not available BOOL FALSE I x UNBAL_VOLT_I DR 130 Phase unbalance voltage REAL 0 0 I x UNBAL_VOLT_I_QC Quality code of UNBAL_VOLT_I BYTE 0 I UNBAL_VOLT_I_OFF DR 130 Phase unbalance voltage OFF BOOL FALSE I x UNBAL_VOLT_I_NA DR 130 Phase unbalance voltage not available BOOL FALSE I x T_UNBAL_VOLT_I DR 130 Delay time for phase unbalance voltage REA...

Страница 38: ...erator input Switch off open the main contacts BOOL FALSE IO x MAN_ON Operator input Switch on close the main contacts BOOL FALSE IO x RESET Operator input trip reset BOOL FALSE IO x RES_MONERR Operator input reset monitoring error BOOL FALSE IO x ACK_TRIP A current trip is acknowledged and reset BOOL FALSE IO x DEL_TRIP Delete trip and event log BOOL FALSE IO x R_VAL_MEM Reset all min max value m...

Страница 39: ... 0 0 O x CUR_L2_QC Quality code of CUR_L2 BYTE 0 O CUR_L3 Current in phase 3 REAL 0 0 O x CUR_L3_QC Quality code of CUR_L3 BYTE 0 O CUR_MAX Current max L1 L2 L3 REAL 0 0 O x CUR_MAX_QC Quality code of CUR_MAX BYTE 0 O CUR_N Current in phase N trip unit REAL 0 0 O x CUR_N_QC Quality code of CUR_N BYTE 0 O U_L1_L2 Voltage line to line L1 L2 A B REAL 0 0 O x U_L1_L2_QC Quality code of U_L1_L2 BYTE 0 ...

Страница 40: ...eeded BOOL FALSE O QWRN 1 A warning signal is currently present BOOL FALSE O QWR_PROT 1 Write operations are prohibited BOOL FALSE O QFREE_COM15 1 Status of the free user input on the COM15 module BOOL FALSE O LST_TRIP Reason for last trip BYTE 0 O QTR_OVLD 1 Overload tripping L BOOL FALSE O QTR_ISC 1 Instantaneous short circuit I BOOL FALSE O QTR_STD_C 1 Short time delay short circuit S BOOL FALS...

Страница 41: ...de of LAST_CHG BYTE 0 O LAST_CHG_NA DR 91 Date of the last parameter change not available BOOL FALSE O N_SC_TRP DR 91 Number of short circuit trips SI WORD 0 O x N_SC_TRP_QC Quality code of N_SC_TRP BYTE 0 O N_SC_TRP_NA DR 91 Number of short circuit trips SI not available BOOL FALSE O x N_OVL_TRP DR 91 Number of overload trips L WORD 0 O x N_OVL_TRP_QC Quality code of N_OVL_TRP BYTE 0 O N_OVL_TRP_...

Страница 42: ...rotective function WORD 0 O DIAG_TRIP_QC Quality code of DIAG_TRIP BYTE 0 O DIAG_SP DR 92 Setpoints warnings DWORD 0 O DIAG_SP_QC Quality code of DIAG_SP BYTE 0 O WRN_NO1 Warning number 1 INT 0 O x WRN_NO2 Warning number 2 INT 0 O x WRN_NO3 Warning number 3 INT 0 O x WRN_NO4 Warning number 4 INT 0 O x WRN_NO5 Warning number 5 INT 0 O x WRN_NO6 Warning number 6 INT 0 O x WRN_NO7 Warning number 7 IN...

Страница 43: ..._DR94_QC Quality code of CUR_L1_DR94 BYTE 0 O CUR_L1_DR94_NA DR 94 Current in phase 1 not available BOOL FALSE O x CUR_L2_DR94 DR 94 Current in phase 2 REAL 0 0 O x CUR_L2_DR94_QC Quality code of CUR_L2_DR94 BYTE 0 O CUR_L2_DR94_NA DR 94 Current in phase 2 not available BOOL FALSE O x CUR_L3_DR94 DR 94 Current in phase 3 REAL 0 0 O x CUR_L3_DR94_QC Quality code of CUR_L3_DR94 BYTE 0 O CUR_L3_DR94_...

Страница 44: ... x VOLT_L3N DR 94 Star voltage phase L3 REAL 0 0 O x VOLT_L3N_QC Quality code of VOLT_L3N BYTE 0 O VOLT_L3N_NA DR 94 Star voltage phase L3 not available BOOL FALSE O x VOLT_DEM_D DR 94 Demand of the delta voltage REAL 0 0 O x VOLT_DEM_D_QC Quality code of VOLT_DEM_D BYTE 0 O VOLT_DEM_D_NA DR 94 Demand of the delta voltage not available BOOL FALSE O x VOLT_DEM_S DR 94 Demand of the star voltage REA...

Страница 45: ... 0 0 O x DEM_RP_L2_QC Quality code of DEM_RP_L2 BYTE 0 O DEM_RP_L2_NA DR 94 Demand of the real power in phase L2 not available BOOL FALSE O x DEM_RP_L3 DR 94 Demand of the real power in phase L3 REAL 0 0 O x DEM_RP_L3_QC Quality code of DEM_RP_L3 BYTE 0 O DEM_RP_L3_NA DR 94 Demand of the real power in phase L3 not available BOOL FALSE O x DEM_AP3 DR 94 Demand of the apparent power 3 phases REAL 0 ...

Страница 46: ...lable BOOL FALSE O x RAP_L1 DR 94 Reactive power in phase L1 REAL 0 0 O x RAP_L1_QC Quality code of RAP_L1 BYTE 0 O RAP_L1_NA DR 94 Reactive power in phase L1 not available BOOL FALSE O x RAP_L2 DR 94 Reactive power in phase L2 REAL 0 0 O x RAP_L2_QC Quality code of RAP_L2 BYTE 0 O RAP_L2_NA DR 94 Reactive power in phase L2 not available BOOL FALSE O x RAP_L3 DR 94 Reactive power in phase L3 REAL ...

Страница 47: ...ity code of PF_L3 BYTE 0 O PF_L3_NA DR 94 Power factor in phase L3 not available BOOL FALSE O x FRQ DR 94 Frequency REAL 0 0 O x FRQ_QC Quality code of FRQ BYTE 0 O FRQ_NA DR 94 Frequency not available BOOL FALSE O x THD_CUR94 DR 94 THD of the current REAL 0 0 O x THD_CUR94_QC Quality code of THD_CUR94 BYTE 0 O THD_CUR94_NA DR 94 THD of the current not available BOOL FALSE O x THD_VOLT DR 94 THD o...

Страница 48: ... OFF BOOL FALSE O x ROV_PH_PH_NA DR 128 Rated operational voltage Phase2Phase not available BOOL FALSE O x SEC_VOLT DR 128 Secondary voltage of the voltage transformer REAL 0 0 O x SEC_VOLT_QC Quality code of SEC_VOLT BYTE 0 O SEC_VOLT_OFF DR 128 Secondary voltage of the voltage transformer OFF BOOL FALSE O x SEC_VOLT_NA DR 128 Secondary voltage of the voltage transformer not available BOOL FALSE ...

Страница 49: ... x T_RP_NORM_NA DR 128 Delay time for real power in normal direction not available BOOL FALSE O x T_RP_REV DR 128 Delay time for real power in reverse direction REAL 0 0 O x T_RP_REV_QC Quality code of T_RP_REV BYTE 0 O T_RP_REV_OFF DR 128 Delay time for real power in reverse direction OFF BOOL FALSE O x T_RP_REV_NA DR 128 Delay time for real power in reverse direction not available BOOL FALSE O x...

Страница 50: ...elay time for THD of the current REAL 0 0 O x T_THD_CUR_QC Quality code of T_THD_CUR BYTE 0 O T_THD_CUR_OFF DR 128 Delay time for THD of the current OFF BOOL FALSE O x T_THD_CUR_NA DR 128 Delay time for THD of the current not available BOOL FALSE O x PU_THD_VOLT DR 128 Pickup THD voltage REAL 0 0 O x PU_THD_VOLT_QC Quality code of PU_THD_VOLT BYTE 0 O PU_THD_VOLT_OFF DR 128 Pickup THD voltage OFF ...

Страница 51: ..._OFF DR 128 Delay time for over voltage OFF BOOL FALSE O x T_OV_VOLT_NA DR 128 Delay time for over voltage not available BOOL FALSE O x PH_UNBL_CUR DR 128 Phase unbalanced current REAL 0 0 O x PH_UNBL_CUR_QC Quality code of PH_UNBL_CUR BYTE 0 O PH_UNBL_CUR_OFF DR 128 Phase unbalanced current OFF BOOL FALSE O x PH_UNBL_CUR_NA DR 128 Phase unbalanced current not available BOOL FALSE O x T_PH_U_CUR D...

Страница 52: ...UT2 DR 128 1 event for the 2nd output BYTE 0 O x EV1_OUT2_QC Quality code of EV1_OUT2 BYTE 0 O EV1_OUT2_OFF DR 128 1 event for the 2nd output OFF BOOL FALSE O x EV1_OUT2_NA DR 128 1 event for the 2nd output not available BOOL FALSE O x EV2_OUT2 DR 128 2 event for the 2nd output BYTE 0 O x EV2_OUT2_QC Quality code of EV2_OUT2 BYTE 0 O EV2_OUT2_OFF DR 128 2 event for the 2nd output OFF BOOL FALSE O ...

Страница 53: ...3 event for the 3rd output not available BOOL FALSE O x EV4_OUT3 DR 128 4 event for the 3rd output BYTE 0 O x EV4_OUT3_QC Quality code of EV4_OUT3 BYTE 0 O EV4_OUT3_OFF DR 128 4 event for the 3rd output OFF BOOL FALSE O x EV4_OUT3_NA DR 128 4 event for the 3rd output not available BOOL FALSE O x EV5_OUT3 DR 128 5 event for the 3rd output BYTE 0 O x EV5_OUT3_QC Quality code of EV5_OUT3 BYTE 0 O EV5...

Страница 54: ... TL_CL_A_QC Quality code of TL_CL_A BYTE 0 O TL_CL_A_OFF DR 129 Time lag class tR PS A OFF BOOL FALSE O x TL_CL_A_NA DR 129 Time lag class tR PS A not available BOOL FALSE O x IN_PRO_PARA_A DR 129 Instantaneous protection parameter li PS A REAL 0 0 O x IN_PRO_PARA_A_QC Quality code of IN_PRO_PARA_A BYTE 0 O IN_PRO_PARA_A_OFF DR 129 Instantaneous protection parameter li PS A OFF BOOL FALSE O x IN_P...

Страница 55: ...QC Quality code of T_EFLT2_A BYTE 0 O T_EFLT2_A_OFF DR 129 Delay time earth fault protection tg2 PS A OFF BOOL FALSE O x T_EFLT2_A_NA DR 129 Delay time earth fault protection tg2 PS A not available BOOL FALSE O x I2T_D_STRIP_A DR 129 I2t curve for delayed S trip PS A BOOL FALSE O x I2T_D_STRIP_A_QC Quality code of I2T_D_STRIP_A BYTE 0 O I2T_D_STRIP_A_OFF DR 129 I2t curve for delayed S trip PS A OF...

Страница 56: ...ad parameter IR parameter PS B not available BOOL FALSE O x OV_LD_N_B DR 129 Overload N phase IN PS B WL REAL 0 0 O x OV_LD_N_B_QC Quality code of OV_LD_N_B BYTE 0 O OV_LD_N_B_OFF DR 129 Overload N phase IN PS B WL OFF BOOL FALSE O x OV_LD_N_B_NA DR 129 Overload N phase IN PS B WL not available BOOL FALSE O x TL_CL_B DR 129 Time lag class tR PS B REAL 0 0 O x TL_CL_B_QC Quality code of TL_CL_B BYT...

Страница 57: ...Earth fault protection parameter lg2 PS B REAL 0 0 O x E_FLT_PROT2_B_QC Quality code of E_FLT_PROT2_B BYTE 0 O E_FLT_PROT2_B_OFF DR 129 Earth fault protection parameter lg2 PS B OFF BOOL FALSE O x E_FLT_PROT2_B_NA DR 129 Earth fault protection parameter lg2 PS B not available BOOL FALSE O x T_EFLT2_B DR 129 Delay time earth fault protection tg2 PS B REAL 0 0 O x T_EFLT2_B_QC Quality code of T_EFLT...

Страница 58: ...de of THERM_T_B BYTE 0 O THERM_T_B_OFF DR 129 Thermal time constant PS B OFF BOOL FALSE O x THERM_T_B_NA DR 129 Thermal time constant PS B not available BOOL FALSE O x LD_SHED DR 129 Load shedding REAL 0 0 O x LD_SHED_QC Quality code of LD_SHED BYTE 0 O LD_SHED_OFF DR 129 Load shedding OFF BOOL FALSE O x LD_SHED_NA DR 129 Load shedding not available BOOL FALSE O x LD_REST DR 129 Load restorage REA...

Страница 59: ... 0 O RP_REV_O DR 130 Real power in reverse direction REAL 0 0 O RP_REV_O_QC Quality code of RP_REV_O BYTE 0 O PF_CAP_O DR 130 Power factor capacitive REAL 0 0 O PF_CAP_O_QC Quality code of PF_CAP_O BYTE 0 O PF_IND_O DR 130 Power factor inductive REAL 0 0 O PF_IND_O_QC Quality code of PF_IND_O BYTE 0 O T_RP_NORM_O DR 130 Delay time for real power in normal direction REAL 0 0 O T_RP_NORM_O_QC Qualit...

Страница 60: ...YTE 0 O RP_DEM_O DR 130 Demand real power REAL 0 0 O RP_DEM_O_QC Quality code of PR_DEM_O BYTE 0 O AP_DEM_O DR 130 Demand apparent power REAL 0 0 O AP_DEM_O_QC Quality code of AP_DEM_O BYTE 0 O T_RP_DEM_O DR 130 Delay time demand of the real power REAL 0 0 O T_RP_DEM_O_QC Quality code of T_RP_DEM_O BYTE 0 O T_AP_DEM_O DR 130 Delay time demand of the apparent power REAL 0 0 O T_AP_DEM_O_QC Quality ...

Страница 61: ...0 O T_CUR_N_O DR 130 Delay time for over current N phase REAL 0 0 O T_CUR_N_O_QC Quality code of T_CUR_N_O BYTE 0 O UNBAL_CUR_O DR 130 Phase unbalance current REAL 0 0 O UNBAL_CUR_O_QC Quality code of UNBAL_CUR_O BYTE 0 O T_UNBAL_CUR_O DR 130 Delay time for phase unbalance current REAL 0 0 O T_UNBAL_CUR_O_QC Quality code of T_UNBAL_CUR_O BYTE 0 O T_CUR_DEM_O DR 130 Delay time for demand of the cur...

Страница 62: ...easurements view miscellaneous tab Diagnosis view warnings tab Diagnosis view trip reason tab Diagnosis view setpoints tab Maintenance view maintenance 1 tab Maintenance view maintenance 2 tab Maintenance view operation tab Protect para view parameter set A Protect para view parameter set B Protect para view additional tab Ext protect para view current tab Ext protect para view voltage tab Ext pro...

Страница 63: ...t MEASUREMENT_CUR Voltage MEASUREMENT_VOLT Active power energy MEASUREMENT_ACT_POW Reactive power energy MEASUREMENT_REACT_POW Apparent power MEASUREMENT_APP_POW Miscellaneous MEASUREMENT_MISC Diagnosis with the tabs Warnings DIAG_WARN Trip reason DIAG_TRIP Setpoints DIAG_SETPOINTS Maintenance with the tabs Maintenance 1 MAINTENANCE_1 Maintenance 2 MAINTENANCE_2 Operation MAINTENANCE_OP Protect pa...

Страница 64: ...cture of the individual views of faceplates is described below The appearance of the faceplates differ depending on whether the 3WL is connected directly to the DP master system or whether it is connected following a Y link When the 3WL is connected following a Y link no data records can be read because the device following a Y link switches to DPV0 mode This explains why faceplate views which onl...

Страница 65: ... Function Manual 11 2008 A5E02316914A 01 63 Standard 1 QMAN_AUT AUT_ON_OP 2 MAN_OFF 3 MAN_ON 4 RESET 5 CUR_L1 6 CUR_L2 7 CUR_L3 8 RES_MONERR 9 QMON_ERR 10 MAINT 11 POS_CB 12 QLOC_OFF ST_CB 13 CUR_MAX 14 ST_CB Figure 3 2 Faceplate for standard view not ready OFF ON tripped Symbol for status ...

Страница 66: ...Yes CUR_MAX Current of phase with maximum load Yes POS_CB Position of circuit breaker Yes MAINT Maintenance mode active inactive Yes QMON_ERR Monitoring error active inactive Yes QMAN_AUT AUT_ON_OP Manual automatic changeover Yes MAN_OFF Switch off circuit breaker operating command Yes MAN_ON Switch on circuit breaker operating command Yes RESET Reset Tripped or Local turn off status Yes CUR_L1 Cu...

Страница 67: ...10 CUR_DEM_L1 11 CUR_L3 12 CUR_L1 Figure 3 3 Faceplate for measurements view current tab Element parameters Meaning Display when 3WL is connected following Y link CUR_L1 Current in phase L1 Yes CUR_L2 Current in phase L2 Yes CUR_L3 Current in phase L3 Yes CUR_N Current in neutral conductor Yes CUR_DEM_L1 Demand for current L1 No CUR_DEM_L2 Demand for current L2 No CUR_DEM_L3 Demand for current L3 ...

Страница 68: ...ARTH_F Current which flows to earth No THD_CUR94 THD of current No Measurements voltage tab MEASUREMENT_VOLT 1 U_L1_N 2 U_L2_N 3 U_L3_N 4 VOLT_DEM_D 5 VOLT_DEM_S 6 VOLT_UNBAL 7 THD_VOLT 8 U_L3_L1 9 U_L2_L3 10 U_L1_L2 Figure 3 4 Faceplate for measurements view voltage tab Element parameters Meaning Display when 3WL is connected following Y link U_L1_L2 Voltage Va b Yes U_L2_L3 Voltage Vb c Yes U_L3...

Страница 69: ...lue of neutral point star voltage No VOLT_UNBAL Phase unbalance voltage as No THD_VOLT THD of voltage No Measurements active power energy tab MEASUREMENT_ACT_POW 1 DEM_RP_L1 2 DEM_RP_L2 3 DEM_RP_L3 4 DEM_RP3 5 SUM_RP 6 ACT_W 7 RE_REV 8 RP_L3 9 RP_L2 10 RP_L1 Figure 3 5 Faceplate for measurements view active power energy tab Element parameters Meaning Display when 3WL is connected following Y link ...

Страница 70: ...d of 3 phase active power No SUM_RP Total active power No ACT_W Active energy in normal direction Yes RE_REV Active energy in reverse direction No Measurements reactive power energy tab MEASUREMENT_REACT_POW 1 RAP_L1 2 RAP_L2 3 RAP_L3 4 SUM_RAP 5 DEM_RAP3 6 REC_E_NORM 7 REC_E_REV Figure 3 6 Faceplate for measurements view reactive power energy tab Element parameters Meaning Display when 3WL is con...

Страница 71: ...direction No Measurements apparent power tab MEASUREMENT_APP_POW 1 AP_L1 2 AP_L2 3 AP_L3 4 DEM_AP_L1 5 DEM_AP_L2 6 DEM_AP_L3 7 DEM_AP3 8 KVA_TOT Figure 3 7 Faceplate for measurements view apparent power tab Element parameters Meaning Display when 3WL is connected following Y link AP_L1 Apparent power in phase L1 No AP_L2 Apparent power in phase L2 No AP_L3 Apparent power in phase L3 No DEM_AP_L1 D...

Страница 72: ...us tab MEASUREMENT_MISC 1 TMP_CUB 2 TMP_MSAE 3 PF_AVG 4 FRQ 5 FORM_F 6 CREST_F 7 PF_L3 8 PF_L2 9 PF_L1 Figure 3 8 Faceplate for measurements view miscellaneous tab Element parameters Meaning Display when 3WL is connected following Y link PF_L1 Power factor in phase L1 No PF_L2 Power factor in phase L2 No PF_L3 Power factor in phase L3 No TMP_CUB Temperature in the control cabinet acc to in COM15 N...

Страница 73: ... 3 WRN_NO3 4 WRN_NO4 5 WRN_NO5 6 WRN_NO6 7 WRN_NO7 8 WRN_NO8 Figure 3 9 Faceplate for diagnosis view warnings tab Element parameters Meaning Display when 3WL is connected following Y link WRN_NO1 1st warning currently active No WRN_NO2 2nd warning currently active No WRN_NO3 3rd warning currently active No WRN_NO4 4th warning currently active No WRN_NO5 5th warning currently active No WRN_NO6 6th ...

Страница 74: ...d shedding warning Load restorage Phase unbalance current µP Error Earth fault warning Over temperature Diagnosis trip reason tab DIAG_TRIP 1 LST_TRIP 2 TRIP_NO Figure 3 10 Faceplate for diagnosis view trip reason tab Element parameters Meaning Display when 3WL is connected following Y link LST_TRIP Trip reason No TRIP_NO Accurate trip reason in event of trip by extended protective function No ...

Страница 75: ... Short time delay short circuit S Ground fault G Trip as a result of extended protection function Overload in neutral conductor Accurate trip reason in event of trip by extended protective function Phase unbalance current Phase unbalance voltage Real power in normal direction Real power in reverse direction Over voltage Under voltage Over frequency Under frequency THD current THD voltage Change of...

Страница 76: ...ement parameters Meaning Display when 3WL is connected following Y link SP_NO1 1st current case of setpoint being exceeded No SP_NO2 2nd current case of setpoint being exceeded No SP_NO3 3rd current case of setpoint being exceeded No SP_NO4 4th current case of setpoint being exceeded No SP_NO5 5th current case of setpoint being exceeded No SP_NO6 6th current case of setpoint being exceeded No SP_N...

Страница 77: ...age Crest factor Form factor Real power in normal direction Real power in reverse direction Demand real power Demand apparent power Demand reactive power Reactive power in normal direction Reactive power in reverse direction Apparent power Over frequency Under frequency Over current Over current earth fault Over current N phase Phase unbalance current Demand current Under voltage Phase unbalance v...

Страница 78: ... MAINT_MC Figure 3 12 Faceplate for maintenance view maintenance 1 tab Element parameters Meaning Display when 3WL is connected following Y link MAINT_MC Maintenance information on the main contacts No N_ACT_LD Number of switches under load No N_ACT_TRP Number of switches caused by trips No N_SC_TRP Number of short circuit releases SI No N_OVL_TRP Number of overload trips L No N_EF_TRP Number of g...

Страница 79: ...ues N No N_ACT_CC Switching cycle counter for On Off switching cycle No OP_HOURS Operating hours counter when On current 0 No RD_DR91 Read maintenance information data record 91 No Maintenance maintenance 2 tab MAINTENANCE_2 1 RD_DR91 2 CON_MOD Figure 3 13 Faceplate for maintenance view maintenance 2 tab Element parameters Meaning Display when 3WL is connected following Y link CON_MOD Modules whic...

Страница 80: ...TU ZSI Module Config dig output module Dig output module 2 Dig input module 2 Breaker Status Sensor BSS Dig output module 1 Dig input module 1 BDA or BDA Plus Grafic display ETU76B Analog output module 2 Analog output module 1 Metering or Metering Plus When the relevant bit is set the corresponding text is displayed in the faceplate Otherwise the field remains empty ...

Страница 81: ...for maintenance view operation tab Element parameters Meaning Display when 3WL is connected following Y link MAINT Maintenance mode active inactive No R_MAINT Reset all maintenance information and counters which can be reset No ACK_TRIP A tripping operation currently active is acknowledged and reset No DEL_TRIP Delete tripping and event log No R_VAL_MEM Reset all min max value memories apart from ...

Страница 82: ...ct para parameter set A tab PARA_SET_A 1 I4T_OVLD_PROT_A 2 PH_L_SEN_A 3 THERM_MEM_A 4 I2T_D_STRIP_A 5 OV_LD_N_A 6 T_EFLT_A 7 T_EFLT2_A 8 RD_DR129 9 I2T_EFLT_PROT_A 10 E_FLT_PROT2_A 11 E_FLT_PROT_A 12 IN_PRO_PARA_A 13 T_STRIP_A 14 SHORT_D_PROT_A 15 TL_CL_A 16 THERM_T_A 17 OV_LD_A Figure 3 15 Faceplate for protect para view parameter set A ...

Страница 83: ..._PRO_PARA_A Short circuit protection instantaneous Isd PS A No E_FLT_PROT_A Ground fault protection Ig1 PS A No E_FLT_PROT2_A Ground fault protection Ig2 PS A No I2T_EFLT_PROT_A I2t characteristic for ground fault protection PS A No I4T_OVLD_PROT_A I4t characteristic for overload protection PS A No PH_L_SEN_A Phase loss sensitivity PS A No THERM_MEM_A Thermal memory PS A No I2T_D_STRIP_A I2t chara...

Страница 84: ...ct para parameter set B tab PARA_SET_B 1 I4T_OVLD_PROT_B 2 PH_L_SEN_B 3 THERM_MEM_B 4 I2T_D_STRIP_B 5 OV_LD_N_B 6 T_EFLT_B 7 T_EFLT2_B 8 RD_DR129 9 I2T_EFLT_PROT_B 10 E_FLT_PROT2_B 11 E_FLT_PROT_B 12 IN_PRO_PARA_B 13 T_STRIP_B 14 SHORT_D_PROT_B 15 TL_CL_B 16 THERM_T_B 17 OV_LD_B Figure 3 16 Faceplate for protect para view parameter set B ...

Страница 85: ..._PRO_PARA_B Short circuit protection instantaneous Isd PS B No E_FLT_PROT_B Ground fault protection Ig1 PS B No E_FLT_PROT2_B Ground fault protection Ig2 PS B No I2T_EFLT_PROT_B I2t characteristic for ground fault protection PS B No I4T_OVLD_PROT_B I4t characteristic for overload protection PS B No PH_L_SEN_B Phase loss sensitivity PS B No THERM_MEM_B Thermal memory PS B No I2T_D_STRIP_B I2t chara...

Страница 86: ...F Figure 3 17 Faceplate for protect para view additional tab Element parameters Meaning Display when 3WL is connected following Y link ACT_PARA Active parameter set No LD_SHED Load shedding warning No LD_REST Load restorage No T_SHED_REST Delay time for load shedding restorage No EARTH_FLT_CUR Type of ground fault detection No STON_GFOFF ZSI short circuit No STOFF_GFON ZSI ground fault No RD_DR69 ...

Страница 87: ...IM 4 RD_DR128 5 THD_CUR 6 PH_UNBL_CUR Figure 3 18 Faceplate for ext protect para view current tab Element parameters Meaning Display when 3WL is connected following Y link PH_UNBL_CUR Current unbalance No THD_CUR THD of current No T_PH_U_CUR Delay time for current unbalance No T_THD_CUR Delay time of THD of current No RD_DR128 Read ext protect para data record 128 No CUR_TRNS_LIM Lower limit of cu...

Страница 88: ...LT 8 PH_UNBAL_VOLT Figure 3 19 Faceplate for ext protect para view voltage tab Element parameters Meaning Display when 3WL is connected following Y link PH_UNBAL_VOLT Voltage unbalance No UNDER_VOLT Under voltage No OVER_VOLT Over voltage No PH_ROT Phase direction of rotation No T_PH_U_V Delay time for voltage unbalance No T_UN_VOLT Delay time for under voltage No T_OV_VOLT Delay time for over vol...

Страница 89: ...128 4 RP_REV 5 RP_NORM Figure 3 20 Faceplate for ext protect para view reactive power tab Element parameters Meaning Display when 3WL is connected following Y link RP_NORM Real power in normal direction No RP_REV Real power in reverse direction No T_RP_NORM Delay time for active power in normal direction No T_RP_REV Delay time for active power in reverse direction No RD_DR128 Read ext protect para...

Страница 90: ...Q 1 T_UN_FRQ 2 T_OV_FRQ 3 RD_DR128 4 OV_FRQ 5 UNDER_FRQ Figure 3 21 Faceplate for ext protect para view frequency tab Element parameters Meaning Display when 3WL is connected following Y link UNDER_FRQ Under frequency No OV_FRQ Over frequency No T_UN_FRQ Delay time for under frequency No T_OV_FRQ Delay time for over frequency No RD_DR128 Read ext protect para data record 128 No ...

Страница 91: ... RD_DR130 9 CUR_THD_I 10 CUR_DEM_I 11 UNBAL_CUR_I 12 CUR_N_I 13 CUR_GRD_I 14 CUR_OVER_I Figure 3 22 Faceplate for setpoints view current tab Element parameters Meaning Display when 3WL is connected following Y link CUR_OVER_I Over current No CUR_GRD_I Current which flows to earth No CUR_N_I Over current in neutral conductor No UNBAL_CUR_I Phase unbalance current No CUR_DEM_I Demand of current No C...

Страница 92: ... No T_UNBAL_CUR_I Delay time for phase imbalance Current No T_CUR_DEM_I Delay time for demand of current No T_CUR_THD_I Delay time for THD current No RD_DR128 Read setpoints data record 130 No WR_DR128 Write setpoints data record 130 No Setpoints voltage tab SETPOINTS_VOLT 1 T_UNDER_VOLT_I 2 T_OVER_VOLT_I 3 T_UNBAL_VOLT_I 4 T_VOLT_THD_I 5 T_CREST_F_I 6 T_FORM_F_I 7 WR_DR130 8 RD_DR130 9 FORM_F_I 1...

Страница 93: ...M_F_I Form factor No T_UNDER_VOLT_I Delay time for under voltage No T_OVER_VOLT_I Delay time for over voltage No T_UNBAL_VOLT_I Delay time for phase imbalance Voltage No T_VOLT_THD_I Delay time for THD voltage No T_CREST_F_I Delay time for crest factor No T_FORM_F_I Delay time for the form factor No RD_DR128 Read setpoints data record 130 No WR_DR128 Write setpoints data record 130 No Setpoints fr...

Страница 94: ... Over frequency No T_UNDER_FRQ_I Delay time for under frequency No T_OVER_FRQ_I Delay time for over frequency No RD_DR128 Read setpoints data record 130 No WR_DR128 Write setpoints data record 130 No Setpoints active power tab SETPOINTS_ACT_POW 1 T_RP_NORM_I 2 T_RP_REV_I 3 T_PF_CAP_I 4 T_PF_IND_I 5 T_RP_DEM_I 6 WR_DR130 7 RD_DR130 8 RP_DEM_I 9 PF_IND_I 10 PF_CAP_I 11 RP_REV_I 12 RP_NORM_I Figure 3...

Страница 95: ...direction No PF_CAP_I Power factor capacitive No PF_IND_I Power factor inductive No RP_DEM_I Demand real power No T_RP_NORM_I Delay time for active power in normal direction No T_RP_REV_I Delay time for active power in reverse direction No T_PF_CAP_I Delay time for power factor capacitive No T_PF_IND_I Delay time for power factor inductive No T_RP_DEM_I Delay time for demand of active power No RD_...

Страница 96: ... 26 Faceplate for setpoints view apparent reactive power tab Element parameters Meaning Display when 3WL is connected following Y link AP_I Apparent power No RAP_NORM_I Reactive power in normal direction No RAP_REV_I Reactive power in reverse direction No AP_DEM_I Demand apparent power No RAP_DEM_I Demand reactive power No T_AP_I Delay time for apparent power No T_RAP_NORM_I Delay time for reactiv...

Страница 97: ...data record 130 No Message suppression 1 SUP_LD_SHED 2 SUP_WRN 3 SUP_SP_EXCEED 4 SUP_OVLD_WRN Figure 3 27 Faceplate for message suppression view Element parameters Meaning Display when 3WL is connected following Y link SUP_OVLD_WRN Message Overload warning present is not output Yes SUP_SP_EXCEED Message An active setpoint has been exceeded is not output Yes SUP_WRN Message There is currently a war...

Страница 98: ...haracteristics Page 102 Block parameters Page 102 Description of symbols and faceplates Page 111 See also Diagnostics block DIA_WLVL Page 17 Driver module DRV_3WL Page 22 3 3 1 Calling OBs The OB watchdog interrupt in which the block is installed e g OB32 Also in OB100 performed automatically in CFC see start up characteristics 3 3 2 Called blocks The block calls the following blocks SFB35 ALARM_8...

Страница 99: ..._ON or AUTO_OFF are always output Under certain circumstances this means that resetting error states may cause a switching operation of the circuit breaker If this is not desired the user must configure the AS program accordingly Switching the circuit breaker on off The user can use the driver block to switch the circuit breaker It is important to note here that the ON state means main contacts cl...

Страница 100: ...er an operation and within the monitoring time TIME_MON the block outputs a message and goes into a resetting state QMON_ERR The faceplate features an appropriate RESET button for resetting this state again NOTICE If the monitoring error is reset the response of the mode must be observed as it may cause a switching operation of the circuit breaker under certain circumstances See Automatic Manual m...

Страница 101: ...being switched back on Maintenance specifications apply to the circuit breakers in accordance with EN 50 110 1 DIN VDE 0105 100 and BGV A2 Protect parameter and extended protect parameter This data which comes from data records 128 and 129 is updated for the display in the faceplate if requested by the operator These parameters cannot be written Setpoints These parameters can be read and written f...

Страница 102: ...4 5 AUX_PR05 6 AUX_PR06 7 AUX_PR07 8 AUX_PR08 9 AUX_PR09 MSG_EVID1 MSG_EVID2 10 AUX_PR10 3 3 5 Assignment of the cyclic process image Only basic type 1 is supported NOTICE This allocation does not match the default allocation of basic type 1 for a VL device Under certain circumstances the allocation in the device therefore has to be adjusted The bytes which deviate from the default allocation are ...

Страница 103: ...e LADDR input is connected to the base address of the 3VL device Procedure Select input parameter right mouse button Interconnection to address Entere g EW512 If 3VL is directly connected to the DP master system the module driver connects block outputs OMODE QRACKF and QMODF to inputs MODE00 RACKF and MODF of the block MOD_PAX0 and the module driver connects input DIAG_INF to output QDIAG_INF of d...

Страница 104: ...ORD 0 I RACKF 1 Rack failure BOOL FALSE I LADDR Base address of 3VL module WORD 0 I BASADR Base address of 3VL module INT 0 I BASADR_OUT Base address of 3VL module for outputs INT 0 I DPA_LINK Device connection 0 DP MASTER 1 DP PA LINK BOOL FALSE I x MSG_LOCK 1 Messages locked BOOL FALSE I x RUNUPCYC Lag Number of run up cycles INT 0 I SAMPLE_T Sample time s REAL 0 0 I CYCLE_T Cycle time of cyclic...

Страница 105: ..._DEM_I DR 130 Demand of the current REAL 0 0 I x CUR_DEM_I_QC Quality code of CUR_DEM_I BYTE 16 80 I CUR_DEM_I_OFF DR 130 Demand of the current OFF BOOL FALSE I x CUR_DEM_I_NA DR 130 Demand of the current not available BOOL TRUE I x T_CUR_OVER_I DR 130 Delay time for over current REAL 0 0 I x T_CUR_OVER_I_QC Quality code of T_CUR_OVER_I BYTE 16 80 I T_CUR_OVER_I_OFF DR 130 Delay time for over curr...

Страница 106: ...nostics BOOL FALSE IO x RD_DR128 Read data record 128 metering and ext protective function BOOL FALSE IO x RD_DR129 Read data record 129 protective function BOOL FALSE IO x RD_DR130 Read data record 130 setpoints BOOL FALSE IO x WR_DR130 Write data record 130 setpoints BOOL FALSE IO x AUT_ON_OP Operator input Mode 1 AUTO 0 MANUAL BOOL FALSE IO x AUX_PR01 Auxiliary value 01 ANY IO AUX_PR02 Auxiliar...

Страница 107: ...E O x MSG_STAT1 Message block 1 STATUS Output WORD 0 O MSG_STAT2 Message block 2 STATUS Output WORD 0 O MSG_ACK1 Message block 1 ACK_STATE Output WORD 0 O MSG_ACK2 Message block 2 ACK_STATE Output WORD 0 O QERR_WR 1 An error occurred during writing DRs BOOL FALSE O QERR_RD 1 An error occurred during reading DRs BOOL FALSE O QWR_STAT Status of DR writing WORD 0 O QRD_STAT Status of DR reading WORD ...

Страница 108: ... FALSE O x STOFF_GFON_QC Quality code of STOFF_GFON BYTE 16 80 O STOFF_GFON_NA Short time off Ground fault on not available BOOL TRUE O x N_ACT_LD DR 91 Number of switch actions under load WORD 0 O x N_ACT_LD_QC Quality code of N_ACT_LD BYTE 16 80 O N_ACT_LD_NA DR 91 Number of switch actions under load not available BOOL TRUE O x N_ACT_TRP DR 91 Number of switch actions caused by a trip WORD 0 O x...

Страница 109: ...OOL TRUE O x CUR_DEM_L3 DR 94 Demand current L3 REAL 0 0 O x CUR_DEM_L3_QC Quality code of CUR_DEM_L3 BYTE 16 80 O CUR_DEM_L3_NA DR 94 Demand current L3 not available BOOL TRUE O x CUR_L1_DR94 DR 94 Current in phase 1 REAL 0 0 O x CUR_L1_DR94_QC Quality code of CUR_L1_DR94 BYTE 16 80 O CUR_L1_DR94_NA DR 94 Current in phase 1 not available BOOL TRUE O x CUR_L2_DR94 DR 94 Current in phase 2 REAL 0 0...

Страница 110: ... O x PH_UNBL_CUR_NA DR 128 Phase unbalanced current not available BOOL TRUE O x PRE_A_OVLD DR 128 Prealarm overload REAL 0 0 O x PRE_A_OVLD_QC Quality code of PRE_A_OVLD BYTE 16 80 O PRE_A_OVLD_OFF DR 128 Prealarm overload OFF BOOL FALSE O x PRE_A_OVLD_NA DR 128 Prealarm overload not available BOOL TRUE O x OV_LD_A DR 129 Overload parameter IR parameter set A PS A REAL 0 0 O x OV_LD_A_QC Quality c...

Страница 111: ... of E_FLT_PROT_A BYTE 16 80 O E_FLT_PROT_A_OFF DR 129 Earth fault protection parameter lg1 PS A OFF BOOL FALSE O x E_FLT_PROT_A_NA DR 129 Earth fault protection parameter lg1 PS A not available BOOL TRUE O x T_EFLT_A DR 129 Delay time earth fault protection tg1 PS A REAL 0 0 O x T_EFLT_A_QC Quality code of T_EFLT_A BYTE 16 80 O T_EFLT_A_OFF DR 129 Delay time earth fault protection tg1 PS A OFF BOO...

Страница 112: ... CUR_OVER_O_QC Quality code of CUR_OVER_O BYTE 16 80 O CUR_GRD_O DR 130 Earth fault current REAL 0 0 O CUR_GRD_O_QC Quality code of CUR_GRD_O BYTE 16 80 O CUR_N_O DR 130 Over current N phase REAL 0 0 O CUR_N_O_QC Quality code of CUR_N_O BYTE 16 80 O CUR_DEM_O DR 130 Demand of the current REAL 0 0 O CUR_DEM_O_QC Quality code of CUR_DEM_O BYTE 16 80 O T_CUR_OVER_O DR 130 Delay time for over current ...

Страница 113: ...aintenance 1 tab Maintenance view operation tab Protect para view protect para tab Protect para view additional tab Ext protect para view Setpoints view Message suppression view Block icon with 1 measurement 1 MAX_CUR Figure 3 28 Symbol with 1 measurement Meaning of measurements Element parameters Meaning MAX_CUR Maximum phase current Faceplate The faceplate available is described in this chapter ...

Страница 114: ...views of faceplates is described below The appearance of the faceplates differ depending on whether the 3VL is connected directly to the DP master system or whether it is connected following a Y link When the 3VL is connected following a Y link no data records can be read because the device following a Y link switches to DPV0 mode This explains why faceplate views which only contain values from da...

Страница 115: ...CS 7 Function Manual 11 2008 A5E02316914A 01 113 Standard 1 QMAN_AUT AUT_ON_OP 2 MAN_OFF 3 MAN_ON 4 RESET 5 CUR_L1 6 CUR_L2 7 CUR_L3 8 RES_MONERR 9 QMON_ERR 10 MAINT 11 QLOC_OFF ST_CB 12 CUR_MAX 13 ST_CB Figure 3 29 Faceplate for standard view not ready OFF ON tripped Symbol for status ...

Страница 116: ...uit breaker tripped Yes CUR_MAX Current of phase with maximum load Yes MAINT Maintenance mode active inactive Yes QMON_ERR Monitoring error active inactive Yes QMAN_AUT AUT_ON_OP Manual automatic changeover Yes MAN_OFF Switch off circuit breaker operating command Yes MAN_ON Switch on circuit breaker operating command Yes RESET Reset Tripped or Local turn off status Yes CUR_L1 Current in phase L1 Y...

Страница 117: ...ON 3WL 3VL for SIMATIC PCS 7 Function Manual 11 2008 A5E02316914A 01 115 Measurements 1 CUR_L2 2 CUR_N 3 CUR_DEM_L2 4 CUR_DEM3 5 CUR_UNBAL 6 CUR_DEM3PH 7 CUR_EARTH_F 8 FRQ 9 CUR_DEM_L3 10 CUR_DEM_L1 11 CUR_L3 12 CUR_L1 Figure 3 30 Faceplate for measurements view ...

Страница 118: ...n phase L3 Yes CUR_N Current in neutral conductor Yes CUR_DEM_L1 Demand for current L1 No CUR_DEM_L2 Demand for current L2 No CUR_DEM_L3 Demand for current L3 No CUR_DEM3 Demand for 3 phase current No CUR_UNBAL Phase unbalance current as No CUR_DEM3PH Mean current value over the three phases No CUR_EARTH_F Current which flows to earth No FRQ Frequency No Diagnosis 1 WRN_NO1 2 WRN_NO2 3 WRN_NO3 4 W...

Страница 119: ...No WRN_NO2 2nd warning currently active No WRN_NO3 3rd warning currently active No WRN_NO4 4th warning currently active No WRN_NO5 5th warning currently active No WRN_NO6 6th warning currently active No WRN_NO7 7th warning currently active No WRN_NO8 8th warning currently active No Possible warnings Pretrip for L Overload Overload N phase Load shedding warning Load restorage Phase unbalance curren...

Страница 120: ..._EF_TRP 6 RD_DR91 Figure 3 32 Faceplate for maintenance view maintenance 1 tab Element parameters Meaning Display when 3VL is connected following Y link N_ACT_LD Number of switches under load No N_ACT_TRP Number of switches caused by trips No N_SC_TRP Number of short circuit releases SI No N_OVL_TRP Number of overload trips L No N_EF_TRP Number of ground fault trips G No RD_DR91 Read maintenance i...

Страница 121: ...re 3 33 Faceplate for maintenance view operation tab Element parameters Meaning Display when 3VL is connected following Y link MAINT Maintenance mode active inactive No R_MAINT Reset all maintenance information and counters which can be reset No ACK_TRIP A tripping operation currently active is acknowledged and reset No DEL_TRIP Delete tripping and event log No R_VAL_MEM Reset all min max value me...

Страница 122: ...ameters Meaning Display when 3VL is connected following Y link OC_LD_A Overload parameter IR parameter set A PS A No TL_CL_A Time lag class tR PS A No SHORT_D_PROT_A Short circuit protection delayed Isd PS A No T_STRIP_A Delay time for short circuit protection tsd PS A No IN_PRO_PARA_A Short circuit protection instantaneous Isd PS A No E_FLT_PROT_A Ground fault protection Ig1 PS A No I2T_EFLT_PROT...

Страница 123: ... protect para data record 129 No Protect para additional tab PROTPARA_ADD 1 EARTH_FLT_CUR 2 RD_DR69 3 RD_DR129 4 STOFF_GFON 5 STON_GFOFF Figure 3 35 Faceplate for protect para view additional tab Element parameters Meaning Display when 3VL is connected following Y link EARTH_FLT_CUR Type of ground fault detection No STON_GFOFF ZSI short circuit No STOFF_GFON ZSI ground fault No RD_DR69 Read ZSI pa...

Страница 124: ... 122 Function Manual 11 2008 A5E02316914A 01 Ext protect para 1 PH_UNBL_CUR 2 RD_DR128 Figure 3 36 Faceplate for ext protect para view Element parameters Meaning Display when 3VL is connected following Y link PH_UNBL_CUR Current unbalance No RD_DR128 Read ext protect para data record 128 No ...

Страница 125: ... 37 Faceplate for setpoints view Element parameters Meaning Display when 3VL is connected following Y link CUR_OVER_I Over current No CUR_GRD_I Current which flows to earth No CUR_N_I Over current in neutral conductor No UNBAL_CUR_I Phase unbalance current No CUR_DEM_I Demand of current No T_CUR_OVER_I Delay time for over current No T_CUR_GRD_I Delay time of current which flows to earth No T_CUR_N...

Страница 126: ...points data record 130 No WR_DR128 Write setpoints data record 130 No Message suppression 1 SUP_WRN 2 SUP_SP_EXCEED 3 SUP_OVLD_WRN Figure 3 38 Faceplate for message suppression view Element parameters Meaning Display when 3VL is connected following Y link SUP_OVLD_WRN Message Overload warning present is not output Yes SUP_SP_EXCEED Message An active setpoint has been exceeded is not output Yes SUP...

Страница 127: ...implest version is depicted and takes the form of a wire jumper between 1 and 2 without customer specific release in released representation Contact 4 5 These User contacts are used to control the magnets for the anti pumping device and or trip detection The circuit breaker should be fitted with the Remote reset magnet for the display and reset button including automatic resetting of the anti pump...

Страница 128: ...ration Manual 4 1 Interconnections on COM15 for 3WL Library SENTRON 3WL 3VL for SIMATIC PCS 7 126 Function Manual 11 2008 A5E02316914A 01 4 1 1 24V DC voltage Figure 4 1 COM15 interconnection at 24V DC voltage ...

Страница 129: ... Manual 4 1 Interconnections on COM15 for 3WL Library SENTRON 3WL 3VL for SIMATIC PCS 7 Function Manual 11 2008 A5E02316914A 01 127 4 1 2 Other voltage levels Figure 4 2 COM15 interconnection at other voltage levels ...

Страница 130: ...erconnections on COM10 for 3VL Library SENTRON 3WL 3VL for SIMATIC PCS 7 128 Function Manual 11 2008 A5E02316914A 01 4 2 Interconnections on COM10 for 3VL 4 2 1 Connection for communication Figure 4 3 Connection for communication ...

Страница 131: ...Interconnections on COM10 for 3VL Library SENTRON 3WL 3VL for SIMATIC PCS 7 Function Manual 11 2008 A5E02316914A 01 129 4 2 2 Connection for motorized operating mechanism Figure 4 4 Connection for motorized operating mechanism ...

Страница 132: ...it of the 3VL circuit breaker such that this is also operated when the main contacts are open Without this supply the ETU would not be able to communicate diagnosis information such as the reason for the last trip if there were no self supply Unlike COM10 the auxiliary and alarm switches are not wired to the COM20 but directly to the ETU and the communication status forwarded to COM20 The followin...

Страница 133: ...ing energy store is needed Note The contact between WE and 24 V must be closed for the remote function Without this wire jumper the PROFIBUS DP cannot be used to switch the SENTRON VL on or off More information on fitting the motorized operating mechanism can be found in the installation instructions for the motorized operating mechanism Connection diagram for COM20 on motorized operating mechanis...

Страница 134: ...01 4 4 Configuring a measuring point 4 4 1 Creating the PLC program The driver block DRV_3WL is integrated into a CFC chart and the LADDR input is connected to the base address of the 3WL device Procedure Select input parameter right mouse button Interconnection to address Enter e g EW512 Figure 4 6 Driver block in CFC chart not connected ...

Страница 135: ...the module driver automatically installs all required driver blocks and connects the driver block The module driver can be called as described below Select Generate module drivers function when compiling the CFC chart Figure 4 7 Compile program Or use Select chart folder right mouse button Generate module drivers Figure 4 8 Generate module driver ...

Страница 136: ... point Library SENTRON 3WL 3VL for SIMATIC PCS 7 134 Function Manual 11 2008 A5E02316914A 01 The driver block connected by the module driver is supplied as the result Figure 4 9 Driver block in CFC chart connected The PLC program has now been created ...

Страница 137: ...e driver block can be connected to WinCC The block icon that is associated with the driver block is used for this purpose that is installed in a process display in the following manner Select Create update block icons function in property dialog of WinCC display Select Derive block icons from Plant View as of PCS 7 V7 0 this tick is set automatically Figure 4 10 Basing the block icons on the plant...

Страница 138: ...Manual 11 2008 A5E02316914A 01 manually in SIMATIC Manager Plant view via selection of technological folder menu Plant hierarchy Create update block icons or Figure 4 11 Creating block icons out of plant hierarchy Automatically create update when compiling the OS Figure 4 12 Create block icons when compiling OS ...

Страница 139: ...Function Manual 11 2008 A5E02316914A 01 137 Manually copy the user object from file Template_SENTRON pdl into the process display and run the Dynamic Wizard Link picture with measuring point Figure 4 13 Link picture component with measuring point The driver block is now fully integrated into WinCC ...

Страница 140: ...Configuration Manual 4 4 Configuring a measuring point Library SENTRON 3WL 3VL for SIMATIC PCS 7 138 Function Manual 11 2008 A5E02316914A 01 ...

Страница 141: ...name Consists of the type of block FB and the number Block length in load work memory Memory requirement of program code once per block type Length of instance data in load work memory Memory requirement of an instance DB Temporary memory The local data memory needed when calling the block in an execution level This is limited depending on the CPU If exceeded you must check this in the CPU configu...

Страница 142: ...n the user program They are saved in the same library Block type name Number Block length in load work memory bytes Length of instance data in load work memory bytes Temporary memory bytes Called blocks DRV_3WL 1741 65666 57090 5434 2372 92 SFB35 SFB52 SFB53 SFC1 SFC6 SFC20 SFC21 DRV_3VL 1740 23050 20014 2414 1172 94 SFB35 SFB52 SFB53 SFC1 SFC6 SFC20 SFC21 DIA_WLVL 1742 1824 1472 322 94 108 SFC6 S...

Страница 143: ...ical problems and other questions If you require technical support or you have questions about the product contact Technical Support Utility Address number Phone 49 0 180 50 50 222 Fax 49 0 180 50 50 223 Internet http www siemens com automation service support Support request www siemens com lowvoltage technical assistance ...

Страница 144: ...Technical support Library SENTRON 3WL 3VL for SIMATIC PCS 7 142 Function Manual 11 2008 A5E02316914A 01 ...

Страница 145: ......

Страница 146: ...wnload catalogs and information material www siemens com lowvoltage catalogs Newsletter always up to date www siemens com lowvoltage newsletter E business in the A D Mall www siemens com lowvoltage mall Online Support www siemens com lowvoltage support Contact for all technical information Technical Assistance Tel 49 911 895 5900 E Mail technical assistance siemens com www siemens com lowvoltage t...