Accessories
4.5 Manual operators
3VA molded case circuit breakers with UL and IEC certification
270
Manual, 01/2019, L1V30435333-01
Locking, blocking or interlocking with cylinder lock (type Ronis)
The cylinder lock (type Ronis) is used, depending on the installation of the cylinder lock
holder, for locking, blocking and interlocking the rotary operators.
●
Locking with cylinder lock (type Ronis):
The cylinder lock (type Ronis) locks the rotary operators in the OFF (O) position.
●
Mutual interlocking with cylinder lock (type Ronis):
Through use of the cylinder lock insert for interlocking, any number of rotary operators
can be mutually interlocked.
This requires that the keys of all opened and locked molded case circuit breakers be
removed and securely stored. Only the key of the rotary operator which is in the ON (I)
position is left in the cylinder lock. This key cannot be removed in the ON (I) position. This
key can only be removed if the rotary operator has been turned to the OFF (0) position,
the cylinder lock has been locked and the molded case circuit breaker has thus been
interlocked. See also chapter Cylinder locks for interlocking multiple 3VA UL molded case
circuit breakers (Page 311).