Description
2.7 Electronic trip unit
3VA molded case circuit breakers with UL and IEC certification
94
Manual, 01/2019, L1V30435333-01
2.7.6
Load acceptance and load shedding - load management
3VA UL molded case circuit breakers equipped with an ETU 3-series or higher series
provide two current thresholds for the purpose of implementing a local load management
function. Load shedding is the upper threshold, and load acceptance the lower threshold.
①
Incoming alarm "load shedding"
⑤
Parameter load acceptance 100 A
②
Outgoing alarm "load shedding"
⑥
Incoming alarm "load acceptance"
③
Parameter load shedding 400 A
⑦
Outgoing alarm "load acceptance"
④
Current in one phase
Note
No trip
Tripping is not initiated as a result of the current value crossing the upper or lower
thresholds.
If the current in one phase exceeds the parameter setting for "load shedding", an incoming
alarm "load shedding" is generated. Only when the current in all three phases drops below
this threshold is an outgoing alarm "load shedding" generated.
The incoming and outgoing alarms can be output via the EFB300 external function box and
transferred via the communication function. Parameterization can also take place via the
"powerconfig" software.
The opposite applies for the load acceptance threshold. If the current in all three phases
drops below the parameter setting, an incoming alarm "load acceptance" is generated. If
only one of the three currents exceeds the parameter setting, an outgoing alarm "load
acceptance" is generated.
To prevent these alarms being generated by brief current peaks and troughs, they can be
delayed by the time t
x
from 1 s to 15 s.